BYPASS TEST PROCEDURE
1.
Disconnect power from the evaporator units .
2.
Loosen the two (2) screws on the front of the grille or duct plenum .
3.
Pull the grille or duct plenum away from the evaporator units .
4.
Remove the screw securing the control panel in place .
5.
Slide the control panel down, out of the evaporator housing . The control panel has two (2) hooks which allow it to attach to
the evaporator units for easy serviceability .
6.
Disconnect the Molex connector labeled #4 .
7.
Locate the bypass plug included in the accessory kit .
8.
Plug the bypass plug into the male Molex connector .
9.
Connect power to the evaporator units . The system should immediately turn on . If all the components are not operational,
disconnect power immediately and contact customer service . If all components seem to be operating correctly, allow the
system to run for four (4) hours . Monitor the temperature of the cellar to determine if the system is cooling properly .
10.
Once the test is complete, remove the bypass plug . Plug the Molex connector back in to the system’s wiring .
11.
Replace the control and faceplate .
NOTE: If instructed by a CellarCool representative, follow the directions below to test the system using the bypass plug provided
in the accessory kit .