Page 54 | 1-800-343-9463
WM&FD TWIN
051019
BYPASS TEST PROCEDURE
NOTE:
If instructed by a CellarCool representative, follow the directions below to test the cooling unit using the bypass plug
provided in the accessory kit.
1.
Disconnect power from the evaporator units.
2.
Loosen the two (2) screws on the front of the grille or duct plenum.
3.
Pull the grille or duct plenum away from the evaporator units.
4.
Remove the screw securing the control panel in place.
5.
Slide the control panel down, out of the evaporator housing. The control panel has two (2) hooks which allow it to attach to
the evaporator units for easy serviceability.
6.
Disconnect the Molex connector labeled #4.
7.
Locate the bypass plug included in the accessory kit.
8.
Plug the bypass plug into the male Molex connector.
9.
Connect power to the evaporator units. The system should immediately turn on. If all the components are not operational,
disconnect power immediately and contact customer service. If all components seem to be operating correctly, allow the
system to run for four (4) hours. Monitor the temperature of the cellar to determine if the system is cooling properly.
10.
Once the test is complete, remove the bypass plug. Plug the Molex connector back in to the system’s wiring.
11.
Replace the control and faceplate.