Ceiec Electric Technology
22
new configuration to the PMC-1380-3 for On-Line programming.
3)
Click <Quit> to leave the PMC-1380-3 Web Console. Please ensure that your changes have been
saved before leaving.
Advanced Settings
Option
Description
Setting
Polling Delay
Time delay between the requests of consecutive Slave IEDs
0 to 60000 ms
Default = 30
Packet Timeout
The maximum waiting time for a response packet
0 to 60000 ms
Default = 1000
Byte Timeout
Specify the maximum amount of time between the
reception of two consecutive bytes before a packet frame is
considered to have ended
0 to 60000 ms
Default = 20
Transmit Delay
Time delay for sending the next request packet after the last
response packet has been received
0 to 60000 ms
Default = 0
Time Sync. Interval
Select how often the Time Sync. Packets are sent
0 to 60000 s
Default = 300
Loop Delay
Time delay between successive scans of the entire loop of
Slave IEDs
0 to 60000 s
Default = 0
Reserved
Enter extended parameters
Null = Default
Notes:
1)
Only experienced personnel should modify the Advanced Settings of the PMC-1380-3.
2)
Click <Submit> at the upper left-hand corner of the right-hand pane to store the new
configuration in a local cache before leaving this page.
3)
Click <Save> at the upper right-hand corner of the web page to save the new configuration to the
device’s configuration file that is stored on the PC for Off-Line programming or to download the
new configuration to the PMC-1380-3 for On-Line programming.
4)
Click <Quit> to leave the PMC-1380-3 Web Console. Please ensure that your changes have been
saved before leaving.
4.6 Driver Management
This option exists in both the On-Line and Off-Line programming modes.