Ceiec Electric Technology
18
Option
Description
Setting
Last Configuration
If the user is running it for first time, the New
Configuration should be used; otherwise, select
Last Configuration
New Configuration
Select the model and then perform configuration
based on its default one
Default:
PMC-1380-3-RR-00-16-
2-N-F0T2-XX-XXXX-E
Import Configuration
Import a backup configuration file
Synchronize Device
Synchronize the PMC-1380-3’s device
configuration to Off-Line Web Console via an
Ethernet connection
IP Address
Enter the static IP address of PMC-1380-3 to
synchronize device configuration
0.0.0.0 to
255.255.255.255
Discover PMC-1380
Discover the IP addresses of all PMC-1380-3 in
LAN to choose
<Enter>
Enter the selected configuration page
4.3 Network Settings
This option exists in both the On-Line and Off-Line programming modes.
Click on Network under Device Settings on the left-hand pane and the following screen appears.
Modify the networking settings based on the actual situation. Click Submit and Save to save your
changes. Please be reminded that the IP addresses for the two Ethernet ports should not be in the
same subnet.
Option
Description
Setting
IP Address
Configure the PMC-1380-3’s IP
address
Default IP1 = 192.168.0.127
Default IP2 = 192.168.1.127
Subnet Mask
Configure the Subnet Mask
Default = 255.255.255.0
Default Gateway
Configure the Default Gateway’s IP
address
Default = 192.168.0.1
Notes:
1)
The IP addresses for the two Ethernet ports must be in different subnets.
2)
The Default Gateway must be in the same subnet as one of the IP addresses.