40
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
RESOUND
SILENCE
RESET
SETUP & PROGRAMMING
Input Function Settings
The panel has two inputs, located on the main circuit board, Class Change (CC) and Alert (PUL). Switching
a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change input
(CC) will cause the alarms to sound
continuously and the Alert input
(PUL) will cause the alarms to pulse.
Either or both of these inputs can
be programmed to have a different
function.
The available functions are:
•
Class Change
(continuous sounder
operation).
•
Alert (pulsing sounder
operation).
•
Evacuate (a latching input which activates all the alarms and shows a general fire indication on the
panel).
•
Silence (for remote silence alarms control).
•
Reset (for remote reset control).
•
Fire Zone 12 (a non-latching input which indicates zone 12 fire LED).
•
Fault Zone 12 (a non-latching input which indicates zone 12 fault LED).
To change the default function of the inputs, enter the above code and press ENTER. The zone 1 fire LED
will illuminate. This indicates setting the function of the CC input.
Use button 1 to move to zone 2 fire LED for setting the function of
the PUL input and then back to zone 1 again.
The current setting for the input will be indicated by the amber, fault
LEDs as per table below.
With the required fire LED lit, as per above, press the ENTER button
Test
Mode
Mute
Buzzer
Test
Lamps
to enter ‘editing mode’. The fire zone 1 LED will now pulse to indicate function 1 (Class
Change).
Test
Mode
Mute
Buzzer
Test
Lamps
Now use button 1 to move the
pulsing fire LED to the required
setting as per the table below, then
use button 2 to select the function.
The amber, fault LED will move to
indicate the new current setting.
Mute
Buzzer
Test
Lamps
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
Class
Change
Alert
Evacuate
Remote
Silence
Alarms
Remote
Reset
Fire Zone
12
Fault Zone
12
Press the ENTER button again to return to input selection.
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
RESET
RESOUND
RESOUND
4
ENTER
4
1
4
1
1
Disable
Mode
2
3
4
ENTER
SILENCE
RESET
1
Disable
Mode
2
3
4
ENTER
SILENCE
1
2
Disable
Test
Mode
Mode
3
@ PSU -
+
28V 0V
+ -
FIRE
C NC NO
FAULT
C NC NO
FR
FLT
-OP -OP
CC
PUL
SNDR1 SNDR2
-IP -IP
+ - + -
ZONE1
+ -
ZONE2 ZONE3 ZONE4
+ - + - + -
Содержание CFX-Plus Pro-Sense 12
Страница 72: ......