25
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
Panel Wide Settings
There are 11 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 11 programmable
options are represented by fire zone LEDs 1 - 11.
Use button 1 to move to option required as per table;
Disable
Mode
Test
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
OPTION 1.
Change / Remove Keypad Access Code
The keypad can be used to activate the panel controls instead of using the key switch. The default code is
1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable
controls, forcing the use of the key switch only.
With the zone 1 fire LED lit, press the ENTER button. Zone 1 fire LED will pulse to indicate
‘edit mode’
and
the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When finished entering the new four-digit code, press the ENTER button. The panel will then confirm the
new code with rapidly pulsing LEDs in sequence and zone 1 fire LED will return to steady ‘view mode’.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3
seconds to exit programming mode 2-1-2-3. (The panel will
confirm the new access code one more time before exiting the
programming mode).
Test
Mode
Mute
Buzzer
Test
Lamps
RESET
RESOUND
ENTER
4
3
2
RESET
SILENCE
RESOUND
2
4
ENTER
2
1
2
3
RESOUND
SILENCE
RESET
1
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
Disable
Mode
SILENCE
1
Disable
Mode
2
3
Fire LED Programming Option
1
Change / remove keypad access code
2
Set number of repeater panels on system
3
Set time for panel delay timer (1 - 10 minutes)
4
Disable battery monitoring
5
Setup internal PCB configuration (adding or removing
extension zone cards)
6
Change network/repeater comms monitoring type
7
Set number of output cards
8
Inhibit muted tone beeps
9
Inhibit network alarms & faults for panel
10
Set number of network slave panels on system
11
Inhibit fire & fault buzzer on network slave panel