33
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
Enter the code
3 1 2 1
and press the ENTER button.
The zone 1 fire LED will light. This indicates setting zone function attributes for zone 1. The amber, fault
LEDs will show the current settings for that zone.
Use button 1 to move to the zone that requires editing.
Test
Mode
Mute
Buzzer
Test
Lamps
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fire zone 1 LED will now pulse to indicate the editing of
attribute 1 (fire latching) for the selected zone.
Use button 1 to scroll to the attribute that requires editing,
indicated by a pulsing fire LED 1 - 9 as per table below.
The setting of the attribute is indicated by the amber, fault LED,
ON or OFF.
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED
(pulsing)
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
Attribute
Fire
latching
Short
circuit as
fire
I.S
operation
Silent
mode
Priority
alarm
Detector
removal
monitoring
Zener
diode
detector
bases
Gate valve
& fire
pump (see
over page)
Delayed
(info only)
Amber
fault LED
(default
setting)
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault LED, then use button 1 to
move to the next attribute if required.
Mute
Buzzer
Test
Lamps
Test
Mode
Mute
Buzzer
Test
Lamps
Press the ENTER button to return back to the zone selection, indicated
by a steady zone fire LED
Disable
Mode
Test
Mode
When finished all the zone function programming, enter the next programming code or disable the controls
and return DIL switch 2 to
‘OFF’.
2
1
ENTER
4
3
2
ENTER
4
3
ENTER
4
3
2
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
3
Mute
Buzzer
4
Test
Lamps
ENTER
RESOUND
SILENCE
RESET
1
Disable
Mode
RESOUND
SILENCE
RESET
1
Disable
Mode
2
3
4
ENTER
1
Disable
Mode
1
2
Disable
Test
Mode
Mode
Содержание CFX-Plus Pro-Sense 12