30
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
OPTION 9
. Inhibit Network Alarms & Faults For Panel
This option prevents any other network
panel’s
alarms or faults from displaying or having any effect on the
panel.
The default setting is ON (panel displays all network alarms & faults and the outputs respond accordingly).
If set to OFF, alarms & faults from other network panels will be ignored. Fires & faults from this panel will
still affect other network panels accordingly.
With the zone 9 fire LED lit, Press the ENTER button. The zone 9 fire LED will pulse ‘edit mode’.
The zone 9 fault LED will be lit (indicates network alarms & faults active).
Press button 1 to change the fault LED to OFF (network alarms & faults inhibited).
When finished press the ENTER button again and the zone 9 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 10
. Set Number of Network Slave Panels on System (Master Panel Only)
If using network slave control panels, the Master panel will need to be programmed with which slave panel
addresses are included in the system, for monitoring purposes. An incorrect quantity will cause a system
fault to be displayed on the panels.
With the zone 10 fire LED lit the amber fault LEDs will display the current slave panel addresses set (0 - 7),
amber fault LED 1 = slave address 01 etc.
Press the ENTER button. The zone 1 fire LED will pulse to indicate adding or removing slave address 01.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fire LED to the required zone (addresses
1 - 7 indicated by zones 1 - 7 respectively).
Then use button 2 to add or remove the slave address, indicated by the amber fault LED ON (added) or
OFF (removed).
Test
Mode
Mute
Buzzer
Test
Lamps
Mute
Buzzer
Test
Lamps
Tip - You can use button 4 as a shortcut to add or remove all 7 addresses in one go.
When finished press the ENTER button again and the zone 10 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
ENTER
4
3
ENTER
4
3
2
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
1
Disable
Mode
1
2
Disable
Test
Mode
Mode