CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
With the required fire LED lit, the amber, fault LEDs will indicate the current timings set. Press the ENTER
button to
enter ‘edit mode’ and the fire LED will change to pulsing.
Now use buttons 1 & 3 to increase or decrease the time. Button 1 increases, button 3 decreases. When
finished press ENTER again to return to ‘view mode’
The confirmation time
1
is indicated by the amber, fault LEDs 1 - 4 (1 - 4 minutes).
The auto reset time
2
is indicated by the amber, fault LEDs 1 - 5 using binary code values. See table below.
Each push will increase or decrease the time by 1 minute.
AMBER LED 1
AMBER LED 2
AMBER LED 3
AMBER LED 4
AMBER LED 5
1 Minute
2 Minutes
4 Minutes
8 Minutes
16 Minutes
EN54 Sounder Resound Options
By default, after an initial fire condition and the (blue) Silence Alarms button has been activated, any new
fire condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the
alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault
LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 to move to the zone for programming (indicated by a pulsing LED) and press the ENTER
button to change the status.
Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see
below). Then use Button 1 to move to the next zone. If the zone has been set to not resound alarms, the
LED will be off. If kept as default, new fire condition will resound alarms, then the LED will be on steady.
Rapid Pulse
= Zone is under selection and is set to have alarms resound (default).
Slow Pulse
= Zone is under selection and has been set to not resound alarms on new fire condition.
LED Off
= Zone has been set to not resound alarms on new fire condition.
LED On
= Zone is set to have alarms resound (default).
Test
Mode
Mute
Buzzer
Test
Lamps
Disable
Mode
Test
Mode
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
2
1
ENTER
4
3
2
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
1
1
1
4
1
Disable
Mode
3
Mute
Buzzer
4
Test
Lamps
ENTER