29
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
OPTION 7
. Set Number of Output Cards
Up to 2 output/relay cards may be added to each control panel to provide additional common or zonal
outputs. The presence of the cards must be setup to enable operation.
With the zone 7 fire LED lit, the amber, fault LEDs (zones 1 - 2) will show the current settings.
Zone 1 amber fault LED ON = Output Card 1, Zone 2 = Output Card 2.
Press the ENTER button, zone 1 fire LED will pulse to indicate adding or removing card 1.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fire LED to the required zone (Cards 1 - 2
indicated by zones 1 & 2 respectively).
Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF
(removed).
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When finished press the ENTER button again and the zone 7 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 8
. Inhibit Muted Tone Beeps
Option to inhibit the intermittent beep that still occurs when a fault or fire tone has been muted using the
Mute Buzzer button.
With the zone 8 fire LED lit, Press the ENTER button. The zone 1 fire LED will pulse ‘edit mode’.
Press button 1 to light the zone 1 fault LED. Beeps are now silenced.
When finished press the ENTER button again and the zone 8 fire LED will return to stea
dy ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
ENTER
4
3
2
1
RESOUND
SILENCE
RESET
RESOUND
SILENCE
RESET
3
Mute
Buzzer
4
Test
Lamps
ENTER
1
2
Disable
Test
Mode
Mode