CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
Programming
The Master panel will need to be programmed for the number of network panels on the system. See panel
wide programming settings, code 2-1-2-3, option 10, (Set Number of Network Slave Panels on System).
Addressing
Each panel needs to have a unique address. The addressing is done using the 4 DIL switches on each of
the Comms PCBs using binary code values, see diagram below.
The addresses should be set in sequence from 1 - 8, first slave panel = address 01, second slave panel =
address 02 etc.
The Master panel is defined by being address 00 (all switches off).
Network slave panels and/or repeater panels are designed to be wired in a fault tolerant (fail safe) loop
configuration, from comms A to B and back to the Master panel again (see drawing below). This enables
the network to still function if there is a break in the cables.
If replacing an older system where the existing cabling cannot be configured in a loop as above, it is
possible to change the panel settings to legacy, radial circuit comms monitoring.
See panel wide programming settings, code 2-1-2-3, option 6, (Change Network/Repeater Comms
Monitoring Type).
!"
#
$#
%#
&#
'
#
!"
#
$#
%#
&#
'
#
."45&31"/&-
ADD 00
4-"7&1"/&-
4-"7&1"/&-
4-"7&1"/&-
4-"7&1"/&-
!"
#
$#
%#
&#
'
#
!"
#
$#
%#
&#
'
#
!"
#
$#
%#
&#
'
#
ADD 01
4-"7&1"/&-
ADD 02
4-"7&1"/&-
ADD 03
ADD 04
4-"7&1"/&-
!"
#
$#
%#
&#
'
#
!"
#
$#
%#
&#
'
#
!"
#
$#
%#
&#
'
#
ADD 05
ADD 06
ADD 07
COMS A COMS B 28 SW -ve OUTPUTS
+ - + -
V+ 1 2 3 4 5 6
COMS A COMS B 28 SW -ve OUTPUTS
+ - + -
V+ 1 2 3 4 5 6
COMS A COMS B 28 SW -ve OUTPUTS
+ - + -
V+ 1 2 3 4 5 6
ON
ON
ON
1
1 2 3 4
1 2 3 4
ADDRESS
ADDRESS
ADDRESS
2 3 4