![CE+T Power TSI VEDA Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/ce-t-power/tsi-veda/tsi-veda_user-manual_2577185008.webp)
8
– TSI VEDA – User manual – v7.1
4. Building blocks
4.1 Inverter
Telecom / Datacom:
-48VDC / 230VAC, 50/60Hz
The TSI Veda is a 600VA/480W (-25 upto +50 deg C), above +50
degree C ,power derated to 500VA/400W(upto +65 deg C) dual port
inverter.
All versions available in REG.
The TSI inverter modules are hot swappable and hot pluggable.
The module operator interface is LEDs showing converter status and output power
Inverter modules run in single phase configurations.
Fan is equipped with alarm and run time meter. The fan is field replaceable.
220 (D) x 139 (W) x 41.5 (H)
1.4 Kg
4.2 Sub-rack
The Veda shelf shall be integrated in min 300mm deep cabinets (recommended 400-600mm),Inch/ETSI mounting.
The Veda shelf house three (3) modules or two (2) inverter m one (1) AC output unit and one (1) monitor unit.
The extension shelf house max three (3) inverter modules and one (1) monitor blank.
The Veda shelf is designed with individual DC input and Common AC output.
Max 1.5kVA per shelf
267 (D) x 19” (W) x 1U (H)
2.1 Kg empty