Fix cage nuts (4) in the mounting frame
Assemble the mounting bracket (3) in a suitable
position.
Slide the shelf in position and fix the shelf with the
supplied screws (5)
Finished
8.2.1 Pre requisites
The sub –rack have markings for all terminations
All cables shall be rated at Min 90 deg C.
Electrical terminations shall be tightened with 1,5Nm
All connection are screw terminals connectors
DC Input-Individual (per module), observe polarity.
AC output –Common (per shelf), respect phases.
Wire all positions in the sub-rack for future expansion
Output AC / Input DC / Signal cables shall be separated
Cable crossings shall be done in 90 deg angles
5
3
14