CE+T Power TSI VEDA Скачать руководство пользователя страница 31

12.2  T1S/T2S

12.2.1  Removal

„

„

Use a small screw driver to release the latch keeping the T1S/T2S in position

„

„

Take care when inserting screw driver in T1S. If tip is not well engaged, there is a chance to damage dip switches 

„

„

Pull the module out

12.2.2  Inserting

„

„

Push the module firmly in place until the latch snaps in position 

12.3  Fan replacement

The FAN life is approx 45.000hours. The inverter modules have fan runtime meters and fan failure alarm. Fan failure can result 
from failing fan or driver circuit.

„

„

Let the module rest at least 5 minutes prior to initiating work.

„

„

The inverter front must be removed. Use a blunt tool to depress the latches on the module side fixing the front to the 
module.

„

„

Remove the fan and unplug the supply cord.

„

„

Replace with new fan and connect supply cord

„

„

Replace front, make sure that the front latch properly.

„

„

Plug in

„

„

Check fan for operation

„

„

Access T2S and reset the fan run time alarm from within the action menu

!!

31 

– TSI VEDA – User manual – v7.1

Содержание TSI VEDA

Страница 1: ...ational patents and trademarks Address CE T S a Rue du Charbonnage 12 B 4020 Wandre Belgium www cet power com info cet power com SINGLE INPUT INVERTER The DC Power as default source AC BACKUP IN A DC...

Страница 2: ...gn 12 7 1 Pack A la Carte 12 7 1 1 Pack 12 7 1 2 A la Carte 12 8 Installation of Veda PACK or Single shelf shelves 13 8 2 Electrical installation Veda PACK or single shelf 13 8 2 1 Pre requisites 14 8...

Страница 3: ...1 Removal 30 12 1 2 Inserting 30 12 2 T1S T2S 31 12 2 1 Removal 31 12 2 2 Inserting 31 12 3 Fan replacement 31 13 AC output distribution 32 13 1 DU connection installation removal 32 13 2 Miniature C...

Страница 4: ...sion REG Regular DSP Digital Signal Processor AC Alternating current DC Direct current ESD Electro Static Discharge MET Main Earth Terminal MBP Manual By pass TCP IP Transmission Control Protocol Inte...

Страница 5: ...n a single action REG systems can be seen as independent power sources To comply with local and international safety standards N output and PE shall be bonded The safety standard IEC EN62040 1 1 requi...

Страница 6: ...abinet by unplugging the inverters Mark inverters clearly with shelf and position for correct Empty inverter positions must not be left open Replace with module or cover 2 2 Other Isolation test must...

Страница 7: ...ronic 3 1 REG mode Inverter modules carrying the TSI logo and the REG mark is a traditional converter DC in AC out Sinusoidal output converted from DC input DC input only The output voltage is always...

Страница 8: ...er Inverter modules run in single phase configurations Fan is equipped with alarm and run time meter The fan is field replaceable 220 D x 139 W x 41 5 H 1 4 Kg 4 2 Sub rack The Veda shelf shall be int...

Страница 9: ...A la Carte monitors max 32 inverters in one bus The T1S provides Alarm monitoring 2 outgoing alarms 2 digital input Dip switch for local setting The T2S provides Alarm monitoring Record the latest 20...

Страница 10: ...optional accessory Veda is suitable for easy integration in 300 400 600 mm depth cabinet 5 2 AC distribution unit 5 2 1 Distribution Rack The standard AC output distribution is designed with a 8X 6A...

Страница 11: ...oom for 1 3 display units and 1 TCP IP agent 6 1 1 Display Backlit 2 line dot matrix The display show two values simultaneous 6 1 2 TCP IP Agent The TCP IP interface board is mounted on the CanDis she...

Страница 12: ...inverter modules 7 1 2 A la Carte The A la Carte is pre assembled and configured as single phase systems The system comprises cabinet inverter sub rack inverter modules monitor device T2S and AC outpu...

Страница 13: ...tput distribution 2 x IEC socket with 10 Amps fuse protection 8 1 Mounting kit Veda PACK or Single shelf The mounting guide rail is adjustable to fit different kind of cabinet depths 8 2 Electrical in...

Страница 14: ...erminations All cables shall be rated at Min 90 deg C Electrical terminations shall be tightened with 1 5Nm All connection are screw terminals connectors DC Input Individual per module observe polarit...

Страница 15: ...Cable min Connector Torque 48VDC Veda pack 16A 2 x 1 5mm2 Screw terminal 1 5Nm VEDA is individual DC feeding On the back the terminal of and are present DC connector are wired as a couple That means t...

Страница 16: ...IEC Socket protected by 10 Amps fues 48VDC 3x1 5mm2 Screw Terminal 1 5Nm 8 2 6 Signalling Relay characteristics Selectable Major Minor Switching power 60W Rating 2A at 30VDC 1A at 60VDC Max wire size...

Страница 17: ...OFF The remote ON OFF can be connected to any shelf The remote ON OFF requires changeover contacts one input opens as the other close If both transitions are not picked up the status is not changed Re...

Страница 18: ...d The internal bus comprise of a 6 pole ribbon cable and an 8 pole ribbon cable The internal bus connectors are sensitive and special caution should be taken during installation to keep them out of ha...

Страница 19: ...e slot and raise the cabinet on location 9 3 Fixing the cabinet to the floor The cabinet is fixed through the base of the cabinet Remove lowest front cover to gain access to the fixing holes Max screw...

Страница 20: ...top cover has support to strap the cables with nylon tie straps Ground PE DC Input X1 Alarm X3 X5 X6 AC Output X4 AC Output distribution X4 DC Input X11 to X18 Alarm X3 Digital in X5 Remote ON OFF X6...

Страница 21: ...ound must be terminated even if commercial mains is not available According to local regulations Min 16mm2 9 4 4 DC input X1 9 4 4 1 Bulk input Common DC input per system Note Screws and nuts are not...

Страница 22: ...9 4 4 2 Individual input Individual DC input per module and return Max 2 5 mm2 per connection terminal Two terminal for one shelf 22 TSI VEDA User manual v7 1...

Страница 23: ...al Cable lug Screw terminal cable lug 1ph Fuse CB Min Cable mm2 Fuse CB Min Cable mm2 1 8 50A 10 3 6 100A 25 16A Live Screw terminal 1 5mm2 Common Ferrule 1 5 mm2 1 5Nm torque 5 4 160A 50 7 2 180A 70...

Страница 24: ...9 4 6 Signalling All relays are in non energized position 24 TSI VEDA User manual v7 1...

Страница 25: ...onnected to any shelf The remote ON OFF requires changeover contacts one input opens as the other close If both transitions are not picked up the status is not changed Digital input characteristics Re...

Страница 26: ...properly Blinking green orange alternatively Recovery mode after boost 10 In short circuit condition Permanent orange Starting mode Blinking orange Modules cannot start Check T2S Blinking red Recover...

Страница 27: ...undancy No Redundancy Redundancy 10 2 1 T1S alarm Description Type 1 Redundancy plus one inverter lost by Major 2 TSI Bus defect Major 3 Incompatability parameter Major 4 Main source lost see configur...

Страница 28: ...S driver CET_T2S inf installed on laptop Available for download at http www acbackuptsi com Username T322010000 Password No password required enter Read T2S manual for detailed setup 11 1 Communicatio...

Страница 29: ...isplay 0 Return to previous menu 1 14 Page number selection 16 Clear log 17 Save log to a file 6 Module errors information 0 Return to preceding menu 1 32 detailled Modules errors 3 System actions sel...

Страница 30: ...ff when opening the handle The handle only fixes the module to the shelf Use a screw driver to release the latch of the handle Open the handle Pull the module out Replace with new module or blind unit...

Страница 31: ...nverter modules have fan runtime meters and fan failure alarm Fan failure can result from failing fan or driver circuit Let the module rest at least 5 minutes prior to initiating work The inverter fro...

Страница 32: ...removal Circuit breakers are normally installed from factory How to add breakers 1 Insert the short connection cable 10mm2 included in the breaker Line side and tighten Up to 40A breaker use one conn...

Страница 33: ...hat all cables are strained relived Make sure that all breakers are according to recommendation and local regulations Make sure that DC polarity is according to marking Re tighten all electrical termi...

Страница 34: ...bserve this rules will result not to have all module operating when running on DC Installation and commissioning must be done and conducted by trained people fully authorized to act on installation It...

Страница 35: ...cording to the site LVD load on AC AC threshold level Switch OFF ACin and check if system is working on DC Not applicable for REG Module Switch ON ACin and check if system correctly transferred load o...

Страница 36: ...hreshold level No output power Check output breaker All OK but I have alarm Check configuration file and correct No of modules Download clear log file No output alarm Mind the default time delay UA 60...

Страница 37: ...nternal temperature for deviation between modules Temperature deviation may indicate build up of dust Clean with compressed air Check module system load Check Correct inverter mapping DC group AC grou...

Страница 38: ...be requested through the http my cet power com extranet Repair registering guidelines may be requested by email at repair cet power com The RMA number should be mentioned on all shipping documents rel...

Страница 39: ...19 Appendix 19 1 Cabinet foot print layout 39 TSI VEDA User manual v7 1...

Страница 40: ...WANDRE T l 04 3456700 Fax 04 3456701 THIS DOCUMENT REMAINS THE PROPERTY OF CE T IT SHALL NOT BE GIVEN TO A THIRD PARTY OR REPRODUCED WITHOUT CE T s AUTHORIZATION 1 2 3 4 5 6 7 8 9 10 11 A B C D E F G...

Страница 41: ......

Отзывы: