10.2 T1S
Alarm indication on T1S (Urgent / Non Urgent / Configurable)
- Green:
No alarm
- Red:
Alarm
Outgoing alarm relay delay
- Urgent
60 seconds delay
- Non urgent
30 second delay
Parameter setting with DIP1 and DIP2.
If inverters are removed for shorter or longer time the T1S must be reset to display valid
alarms, unplug T1s and reinsert for a reset.
Parameter set up (other than factory default) requires the use of T2S as an installation tool, see System set up
In three phase applications replacement and extension inverter modules must be configured T2S
Category
Left position
Right position
DIP 1
Digital in detection
Open for active
Close for active
DIP 2
Redundancy
No Redundancy
Redundancy
10.2.1 T1S alarm
Description
Type
1
Redundancy plus one inverter lost by
Major
2
TSI Bus defect
Major
3
Incompatability parameter
Major
4
Main source lost (see configuration done by T2S)
Major
5
At least one digital input activated (*2)
Major
6
Redundancy lost
Minor
7
Secondary source lost
Minor
8
At least one invert in alarm
Minor
10.3 T2S
Alarm indication on T2S (Urgent / Non Urgent / Configurable)
- Green:
No alarm
- Red:
Alarm
- Flashing Exchanging information with inverters (only Configurable alarm)
Outgoing alarm relay delay
- Urgent
60 seconds delay
- Non urgent
30 second delay
Parameter setting via Laptop or Copy/Paste.
Factory default according to list of set values, see Table of set values
Major Alarm
Minor Alarm
DIP Switch 1
DIP Switch 2
Major Alarm
Minor Alarm
User selectable Alarm
USB port
27
– TSI VEDA – User manual – v7.1