13. AC output distribution
13.1 DU connection installation/removal
Output connection is provided with 8 IEC connector which is connected to each 6A rated breaker
IEC connector can be plugged in for the output connection of load cable
unplugged for removing output connection
Switch breaker ON
13.2 Miniature Circuit breaker installation/removal
Circuit breakers are normally installed from factory.
How to add breakers
1.
Insert the short connection cable (10mm2 (included)) in the breaker Line-side and tighten.
- Up to 40A breaker use one connection cable.
- 63A breaker use two connection cables.
2.
Clip breaker on to the DIN rail
3.
Insert Insulated screw driver in the terminal to load the spring
4.
Insert connection cable and remove screw driver
5.
Connect load cable to breaker, Neutral and Ground
6.
Switch breaker ON
7.
Remove breaker in reverse order
32
– TSI VEDA – User manual – v7.1