8.2.2 Terminations
All terminations are clearly marked.
8.2.3 Grounding
“PE CHASSIS GROUND”
PE Chassis ground shall be wired to MET or distributed earth bar connected to MET
According to local regulations.
8.2.4 DC input
CB per module
Cable, min
Connector
Torque
-48VDC Veda pack
16A
2 x 1.5mm
2
Screw terminal
1.5Nm
VEDA is individual DC feeding. On the back the terminal of ( + ) and ( - ) are present. DC connector are wired as a couple. That
means that the first right ( - ) terminal and the first ( + ) terminal correspond to the left inverter on the front. Same thing for
center ( - ) terminal and the center ( + ) terminal correspond to the center inverter on the front, etc.