background image

365

UPO33

5<<

>>6

2.3.  Battery Handling

2.4.  Installation, operation and maintenance handling

3. GENERAL DESCRIPTION

• When installing the UPS with flexible cables with a length sufficient to 

enable the team to move in such a way that is accessible from all sides to 

perform any service.

Batteries are elements with high energy storage capacity and generates 

dangerous voltages within the UPS, even while disconnected from the power 

supply unit of input, so both the team and their batteries should only be 

operated by qualified personnel and take preventive measures listed below:

• Remove watches, rings and other metal objects.

• Use only tools with insulated handles.

• To change batteries, install the same amount and same type of batteries.

• Replace battery fuse only with same type and same rating.

• Do not open, or destroy, or burn batteries, the electrolyte may cause injury 

to the skin and eyes. It is highly toxic. If exposed to fire may explode

• Disposal of batteries must be in accordance with relevant environmental 

standards.

Here are some safety recommendations during installation, operation and 

maintenance of the UPS:

• All work must be intervention at UPS Realize by qualified personnel.

• Prior to installation of the equipment must verify that all breakers are in the 

OFF position, mainly batteries and must be handled only when the UPS is 

completely interconnected to rush for strict compliance to the procedure 

described in this manual.

• Remove the caps from the UPS and check that all internal components are 

in perfect condition, while checking the fit of connectors

Here are some safety recommendations during installation, operation and 

maintenance of the UPS:

• All work must be intervention at UPS Realize by qualified personnel.

• Prior to installation of the equipment must verify that all breakers are in the 

OFF position, mainly batteries and must be handled only when the UPS is 

completely interconnected to rush for strict compliance to the procedure 

described in this manual.

• Remove the caps from the UPS and check that all internal components are 

in perfect condition, while checking the fit of connectors

The UPO CDP Phase UPS provides AC power 33 to power equipment that 

requires a good quality of energy such as computer equipment, communica-

tions, servers, data networks, electrical equipment (not recommended for 

equipment used for life support) etc. automation systems.

The PWM ON-LINE double conversion UPS provides free energy of the 

main problems of the grid, such as blackouts, sudden changes in voltage 

and / or frequency, power surges, brownouts, noise, transients, harmonic 

distortion, etc. 

The device has a user friendly interface, which displays the UPS status 

easily. It also has an LCD screen through which you can consult various 

UPS parameters such as voltages in each phase, frequency, temperature, 

current, etc.

The device has an RS232 interface which allows system monitoring from a 

PC. As optional devices can include an SNMP device or a cellular modem. 

The latter two can monitor the UPS from a remote location via the Internet.

O&!

OS!

'&&!

OS!

%&&!

 

 

 

h

 We recommend using a three-phase industrial breaker. 

TABLE 4.2. CROSS SECTIONS OF THE WIRES TO THE OUTPUT OF THE UPS 

IB9BIJKL!

M@AB3!

9B:NO!FB8FO!M==3!

PO8KQBR!

FB8FO!M==3!

FQS8PT!FB8FO!

M==3!

KNQOOU9NB:O!

VQOB@OQW!

%&!

O!

'&!

'&!

H&!

6&!

'6!

%S!

%'!

N&!

H&!

%'!

6&!

%S!

WS!

N&!

6S!

N&!

S&!

''S!

O&!

NS!

'&&!

OS!

'S&!

 

h

 We recommend using a three-phase industrial breaker. 

?":"+GHEFBA2DEIJ9

 

 

To access the terminals in the ups of 20 kva to 30 kva, remove the back cover. the terminals are at the 

bottom. in the ups of 40 kva to 80 kva, the terminals are located on the front face. to access them you must 

first open the front cover and then remove the cap covering the terminals (see figure 2.3), which is located 

below the transient suppressor. figure 4.3 shows the connection terminals.

 

!

!

3;<D?J!H(6(!+B88JE>;B8!>J?C;8#:@!

 

P@)%F=BD<G:;

 

K"!"+G0%,-0'+/$%<'

 

GP 33 UPS  includes a control panel that displays the status of the ups, and to see certain parameters on a 
lcd screen (input voltage, output voltage, frequency, temperature, etc). figure 5.1 shows that interface. 

Содержание UPO33

Страница 1: ...ual Three PhaseUPS WithIntegratedMonitoringSystem CHICAGO DIGITAL POWER Chicago Digital Power Incorporated 1193 W Higgins Elle Groove Village Il 60007 Tel 847 718 9545 Fax 847 718 9546 www cdpups com 365 UPO33 ...

Страница 2: ...r to implementation 6 OPERATING PROCEDURES 6 1 Comissioning 6 2 Total Shutdown 6 3 Normal to electronic bypass transference 6 4 Manual Bypass 6 5 Alarm Reset 7 OPERATION 7 1 Control Panel 7 2 Front cover lights 7 3 LCD operation 7 4 UPSmenudescription 27 7 5 Emergency shutdown 8 ALARMS 8 1 Active alarms 8 2 Alarm reset and UPS normalization 9 COMMUNICATIONS 9 1 RS 232 port 9 2 Net adapter Optional...

Страница 3: ... upright Upon receipt of the check the packaging machine which must be in perfect condition no hits no breaks free from excessive moisture otherwise immediately notify the carrier and our company During storage of ups it must be placed in a suitable place where not exposed to direct sunlight or near heat sources such as boilers stoves etc As one should not store near water pipes or in wet envi ron...

Страница 4: ... the fit of connectors Here are some safety recommendations during installation operation and maintenance of the UPS All work must be intervention at UPS Realize by qualified personnel Prior to installation of the equipment must verify that all breakers are in the OFF position mainly batteries and must be handled only when the UPS is completely interconnected to rush for strict compliance to the p...

Страница 5: ...ver Lights Communication ports RS232 and RJ 45 optional Cooling slots Frontal Panel Lock Front cover lights Communications ports RS232 and RJ 45 optional Cooling Slots Transient supressor Dual Input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Battery breaker Transient supressor Dual input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Batt...

Страница 6: ...KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B8 E U EK V J9 B8 2 d 0KJ K BAJ B8 CB9J UKJ8 KJ J U BCJ B BF BTJ B 9 KJ BD AD KJ J U J J 89 VBTJ KJ 8BC 8 T DJ BF BAJ B8 B KJ V J VJ8EK BB CDEK 9 EK J9 1IFD 8 C 8D V A CB9J UKJ8 KJ B 9 EB88JE J9 9 JE B KJ C 8 K BD K V A E ED K J KJ G42 J F JC 8 D8J8J XJ9 0K CB9J BU KJ D J B BAJ B B E BD E J B GJ 1IFD 18 K BAJ B8 CB9J KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B...

Страница 7: ... inside the UPS is above the nominal value of operation or when the battery pack is deeply discharged In this state the load is powered from the network through the bypass breaker When the UPS is in manual bypass the load is supplied directly from the network through the bypass breaker while the UPS remains de energized This allows maintenance on the UPS without interrupting power to the load In f...

Страница 8: ... the input of the UPS before the bat estuaries discharge 5 Press the OFF for five seconds 6 Press the ON for more than six seconds 7 See procedure in Section 6 4 8 See procedure in Section 6 4 9 See procedure in Section 6 2 10 See procedure in Section 6 1 11 Turn off the bypass breaker 12 Switch the bypass breaker 13 When it returns to the input energy and the batteries are discharged 14 See proce...

Страница 9: ... 208 VAC There must be a unique breaker to the UPS distribution panel Each line entry and exit should have adequate thickness to withstand the current passing through it The current driving the UPS and hence the sizes of the wires at the entrance and exit agreements changes do to their ability as shown in the following tables FIGURE 4 1 UPS PACKAGING FIGURE 4 2 UPS ANCHORED TO THE PALLET 1 A79 ABC...

Страница 10: ...itches are turned off Check that all loads are off Check the polarity of the battery bank h We recommend using a three phase industrial breaker GHEEBGFDHE FBA2DEIJ9 To access the terminals in the ups of 20 kva to 30 kva remove the back cover the terminals are at the bottom in the ups of 40 kva to 80 kva the terminals are located on the front face to access them you must first open the front cover ...

Страница 11: ...ILURE and you will hear a beep If this is the case check that batteries are properly connected and the battery breaker is on If when installing the UPS was an error in the phases connection turning on the UPS on the screen appears an alarm FAILURE SEQUENCE BYPASS In this case the UPS will not operate in bypass mode but it will operate in normal mode of operation To solve the problem correctly conn...

Страница 12: ...have the correct polarity Turn the output breaker At this point will begin to supply the load through the bypass Turn the manual bypass breaker For the UPS is operating in normal mode press the ON for more than a second It is recommended that the bypass breaker manipulation is done by quali fied personnel 6 5 Alarm Reset See section 8 2 The UPS UPO33 includes a control panel that displays the stat...

Страница 13: ...he lights are reds means that the load is being fed to the energy stored in batteries if the lights are flashing red and blue is because the charger is not working properly the cause may be who missed one or two phases to the entrance when the charger starts and if there is no problem the lights are flashing blue and violet if you used the emergency shutdown of the ups the light has a violet color...

Страница 14: ... batteries IF the lights are flashing red and blue is because the charger is not working properly The cause may be that missed one or two steps at the entrance When the charger starts and there is no problem if the lights are flashing blue and violet If you use the emergency shutdown of the UPS the light has a violet color 7 3 LCD operation In Figure 7 2 illustrates the operation of the LCD and in...

Страница 15: ... all three phases and frequency Table 5 2 Description of the UPS menus 0 4 E H C 8 CJ8D This is the main menu display this screen shows the ups operating status in this case is in normal operation it also displays the web address of manufacturer date and time in this menu you can also update the date and time to make it do the following press three times the enter esc button and the last two digit...

Страница 16: ...and the batteries are discharged the causes may be dc fuse open loss of any of the input phases input voltage phase neutral outside the operating range 80 to 150 volts rms check the input voltages call for service RECTIFIER TURN ON is on the battery charger 8 INVERTER TURN ON The invertir is turned on 8 MANUAL INV SHUTDOWN inverter has been turned off manually 8 EMERGENCY PWR OFF emergency shutdow...

Страница 17: ...D the ups batteries are depleted one possible cause is that the ups has operated in battery mode for long wait for the ups input is normal and start charging the batteries if after the input is normal the battery will not charge call service DC FUSE BLOWN the dc fuse is open this happens when you turn the battery breaker before you turn on the charger when you are starting the ups support call 5 V...

Страница 18: ...battery warning 8 CHECK FANS the blowholes are more than 5 years of use it is advisable to change the FANS to perform the operation contact technical support SELFDIAGNOSTIC alarm information indicates that event counters ups have flooded the memory limit note this does not imply a malfunction of the machine diagnostic is recommended by software call support PWR SUPPLY WARNING it is activated when ...

Страница 19: ...ppears when you turn on the ups 8 TEMPERATURE ALERT this alarm occurs when there is a high temperature in the computer but not high enough to go to bypass check the temperature of where the ups is located check the air conditioning system because it may be a fault AMBIENT TEMP OK it is activated when the temperature is at an optimum level after having been high 8 START BATTERY TEST has been initia...

Страница 20: ...inverter overflow of the investor check for shorts to the output verify that the load does not consume more power than it is capable of supplying the ups check the temperature of where the ups is located avoid charges that generate large surges in short time if the problem persists call service Ij4 3 Q G0 3 L the frequency of the input bypass is not adequate to power the loads wait until the frequ...

Страница 21: ...nd using a USB to serial converter TRENDnet TU S9 Monitoring can be done from a PC using HyperTerminal which is included in Windows versions less than or equal to Windows XP For more recent versions can be down loaded from the Internet Give the connection a name and select an icon and click OK Then in the next window in the Connect using select the port where the UPS is connec ted and click OK see...

Страница 22: ...1 4 Click on the button off and then Properties Then see the window shown in Figure 9 1 5 Select the Settings tab and click on the ASCII Setup see Figure 9 1 6 In the next window select the Add linefeed at the end of each line received and click OK to see the window in Figure 9 1 4 and click on the button call ...

Страница 23: ...s Additionally provide the UPS MIB to adapt to an environment with a professional monitoring NMS program such as OpenView If allowed the UPS is able to send E MAIL s warning to 8 different email addresses in case of abnormal operating conditions including cell phone numbers The cellular modem allows a GSM network to monitor the UPS status This system allows real time knowledge of the behavior of e...

Страница 24: ... normally closed switch thus complementary signals For example when the UPS inverter is operating normally the normally open switch is open and normally closed switch is closed If the inverter fails the normally open switch closes and the normally closed switch will open With the ability to customize the UPS is easy to adapt the UPS to the particular characteristics of virtually any power plant Th...

Страница 25: ...oundingsystemgenerally verifyingthattheneutralofthetransformersecondaryoverallsystempowerisreferenced tothispoint Theinputandoutputconductorsmustberoutedtogethertoavoidfeedback andachieveelectromagneticcompatibility Itmustestablishthattheminimumdistancesofventilation maintenanceandoperationof theUPStothewallsorbarriersaround mustbeatleast500mm 50cm Theboardshouldhavearegulatedinsulatedneutralbusba...

Страница 26: ...ls parts components and labor II CHICAGO DIGITAL POWER OF MEXICO SA DE CV will repair the product and if your judgment is not beyond repair to change the team and the defective parts and components thereof without charge to the owner during the warranty period and the cost reasonably incurred transportation of the product resulting from compliance III The repair time will not exceed thirty days fr...