INTRODUCTION
2. SECURITY RECOMENDATIONS
365
UPO33
3<<
>>4
UPS
•
Temperature:
0° C a 40°C.
•Relative Humidity:
0% a 95% withoutn condensation.
Battery
•
Temperature:
0°C a 25°C.
•Relative Humidity:
0% a 95% without condensation.
2.2. Minimum conditions for UPS location
2.1.
Handling, transporting and storaging
The purpose of this manual is to provide all persons involved in the
various processes of handling, transport, installation and operation of
the UPS, the information needed to handle the machine properly and
safely for both the UPS and the equipment that it protects, and for
those who interact with it. Any question or suggestion that may arise
while reading this manual, please contact us, we will look to solve their
requirements.
During handling, transport and storage of equipment prior to installation
keep it in its original packaging to protect it from shocks, impacts and
harmful environmental conditions.
It is important to note that the UPS usually exceeds 200 kg (see the
weight of the unit in the table of technical specifications) and should
only be handled with appropriate equipment for lifting and handling
heavy loads. In addition, always be kept upright
Upon receipt of the check the packaging machine which must be in
perfect condition, no hits, no breaks, free from excessive moisture,
otherwise immediately notify the carrier and our company.
During storage of ups, it must be placed in a suitable place, where
not exposed to direct sunlight or near heat sources such as boilers,
stoves, etc. As one should not store near water pipes or in wet envi-
ronments. The height above sea level can affect equipment perfor-
mance. The UPS and its batteries require the following storage condi-
tions:
If the UPS is stored for longer than three months is necessary to
charge the batteries to prevent irreparable damage to them and there-
fore the loss of the guarantee of the same.
The place will be installed the UPS must meet the following minimum require-
ments:
• The same conditions recommended for storage.
• For purposes of ventilation equipment should be left between the wall and
the back of the UPS an area of at least 30 cm. For purposes of maintaining a
1 meter around the system would be adequate.
• The ambient temperature must not exceed 25 ° C, as this is the maximum
operating temperature recommended by battery manufacturers. Higher
temperature levels affect their lifetime, leading to decrease by half if they
operate above 30 degrees.
• If there is air conditioning, be sure not to generate condensation.
FIGURE 4.1 UPS PACKAGING
FIGURE 4.2 UPS ANCHORED TO THE PALLET.
?"1"+A79#+ABC7DAB2BEF9
The GP 33 ups requires a three phase input 3x220/380 vac. you must have a dedicated breaker for the ups
distribution panel. each line in the entry and exit must have the proper gauge to carry the current to flow
through them.
The sizes of the cables at the input and output change according to capacity, as shown in the following tables.
Table 4.1 gauges of the wires to the ups input.