REVO RT
from 35A to 90A
User’s manual
39
P48 - Hysteresis Loop 1 (Address ModBus 2048)
P62 - Hysteresis Loop 2 (Address ModBus 2062)
P76 - Hysteresis Loop 3 (Address ModBus 2076)
Hysteresis value for control, when process control is ON/OFF type
-10000 ÷ +10000 [digit] with analog input
-1000.0 ÷ +1000.0 ° with thermocouple
Default:
0.2.
P49 - Percentage of exit with error input Loop 1 (Address ModBus 2049)
P63 - Percentage of exit with error input Loop 2 (Address ModBus 2063)
P77 - Percentage of exit with error input Loop 3 (Address ModBus 2077)
Fixed output percentage in case of input sensor error
If configured in Heating/Cooling, the negative value indicates the percentage of the cooling output.
-100% ÷ +100% Percentage of control output.
Default:
0%.
P50 - Input error control type Loop 1 (Address ModBus 2050)
P64 - Input error control type Loop 2 (Address ModBus 2064)
P78 - Input error control type Loop 3 (Address ModBus 2078)
Selects the operating mode of the error control function
When active it forces the output to the value contained in parameter 49
0
1
Error generated by loop 1 probe failure (
Default
)
Error generated by breakage of any probe
P51 - Percentage of output when in Stop Loop 1 (Address ModBus 2051)
P65 - Percentage of output when in Stop Loop 2 (Address ModBus 2065)
P79 - Percentage of output when in Stop Loop 3 (Address ModBus 2079)
Fixed percentage of control output with controller in STOP mode
If configured in Heating/Cooling, the negative value indicates the percentage of the cooling output.
-100% ÷ +100% Percentage of control output.
Default:
0%.
P52 - Enabling storage Manual status Loop 1 (Address ModBus 2052)
P66 - Enabling storage Manual status Loop 2 (Address ModBus 2066)
P80 - Enabling storage Manual status Loop 3 (Address ModBus 2080)
If enabled, on switching on the regulator will return to the automatic or manual mode prior to switching off, also maintaining
any output percentage.
If in automatic operation, in the event of a probe breakage, the regulator will switch to manual mode, maintaining the value
of the output percentage generated by the PID immediately before the breakage.
0
1
Disabled (
Default
)
Enabled
P53 - Eco Mode
ECO
function enabled for all Loops (Address ModBus 2053)
Function can only be enabled in single-phase mode (see Par P43)
It manages the active zones using the cycle time of loop 1 at all times, staggering the activation of loop 2 and 3 outputs by 1/3
of the cycle time. By doing so, as long as the output percentage remains below 33.3% the outputs will not overlap.
0
1
Disabled (
Default
)
Enabled