36
REVO RT
from 35A to 90A
User’s manual
Configuration parameter list
10.1 Analog Input
P1 – Input Type Loop 1 (Address ModBus 2001)
P15 - Input Type Loop 2 (Address ModBus 2015)
P29 - Input Type Loop 3 (Address ModBus 2029)
Analog input configuration / AI1 sensor selection
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Tc-K
Tc-S
Tc-R
Tc-J
Tc-T
Tc-E
Tc-N
Tc-B
0-1
0-5
0-10
0-20
4-20
0-60
-260° C ÷ 1360° C (
Default
)
-40° C ÷ 1760° C
-40° C ÷ 1760° C
-200° C ÷ 1200° C
-260° C ÷ 400° C
-260° C ÷ 980° C
-260° C ÷ 1280° C
100° C ÷ 1820° C
0 ÷ 1 V
0 ÷ 5 V
0 ÷ 10 V
0 ÷ 20 mA
4 ÷ 20 mA
0 ÷ 60 mV
P2 - Lower limit Loop 1 (Address ModBus 2002)
P16 - Lower limit Loop 2 (Address ModBus 2016)
P30 - Lower limit Loop 3 (Address ModBus 2030)
Lower limit of the analog input
Example: with 4 ÷ 20 mA input this parameter assumes the value associated with 4 mA.
-32767 ÷ +32767 [digit]
Default:
0
P3 - Upper limit Loop 1 (Address ModBus 2003)
P17 - Upper limit Loop 2 (Address ModBus 2017)
P31 - Upper limit Loop 3(Address ModBus 2031)
Upper limit of the analog input
Example: with 4 ÷ 20 mA input this parameter assumes the value associated with 4 mA.
-32767 ÷ +32767 [digit]
Default:
1000
P4 - Over Limits Loop 1 (Address ModBus 2004)
P18 - Over Limits Loop 2 (Address ModBus 2018)
P32 - Over Limits Loop 3 (Address ModBus 2032)
When set as a linear input, it allows the process to exceed its limits (Par. P2 and P3)
0
1
Disabled (
Default
)
Enabled
10
Содержание REVO RT
Страница 2: ......