REVO RT
from 35A to 90A
User’s manual
43
P100 - Maximum output percentage limit Loop 1 (Address ModBus 2100)
P126 - Maximum output percentage limit Loop 2 (Address ModBus 2126)
P152 - Maximum output percentage limit Loop 3 (Address ModBus 2152)
Maximum value of power output percentage
0% ÷ 100%
Default:
100%
P101 - Maximum deviation for SelfTune activation Loop 1 (Address ModBus 2101)
P127 - Maximum deviation for SelfTune activation Loop 2 (Address ModBus 2127)
P153 - Maximum deviation for SelfTune activation Loop 3 (Address ModBus 2153)
When the automatic PID calculation is active (Self Tune), this parameter sets the maximum process-setpoint
deviation beyond which the automatic tune recalculates the PID parameters.
8 ÷ 10000 [digit]
0,8 ÷ 1000.0° with thermocouple.
Default:
2.0
P102 - Minimum proportional band Loop 1 (Address ModBus 2102)
P128 - Minimum proportional band Loop 2 (Address ModBus 2128)
P154 - Minimum proportional band Loop 3 (Address ModBus 2154)
Minimum proportional band value for automatic PID calculation (Pretune)
0 ÷ 10000 [digit]
0,0 ÷ 1000,0° with thermocouple
Default:
3.0
P103 - Maximum proportional band Loop 1 (Address ModBus 2103)
P129 - Maximum proportional band Loop 2 (Address ModBus 2129)
P155 - Maximum proportional band Loop 3 (Address ModBus 2155)
Maximum proportional band value for automatic PID calculation (Pretune)
0 ÷ 10000 [digit]
0,0 ÷ 1000,0° with thermocouple
Default: 100.0
P104 - Minimum Integral Time Loop 1 (Address ModBus 2104)
P130 - Minimum Integral Time Loop 2 (Address ModBus 2129)
P156 - Minimum Integral Time Loop 3 (Address ModBus 2156)
Minimum integral time value for automatic PID calculation (Pretune)
0.0 ÷ 1000.0 sec
Default: 30.0 sec
P105 - Overshoot function level Loop 1 (Address ModBus 2105)
P131 - Overshoot function level Loop 2 (Address ModBus 2131)
P157 - Overshoot function level Loop 3 (Address ModBus 2157)
The level of the overshoot function prevents overshoot when the setpoint is reached or changed.
If the overshoot is set too low, the overshoot may not be fully absorbed, while too high a value may cause the process to
reach the setpoint more slowly.
0 Disabled
1 ÷ 10 [Lev.1 ÷ Lev.10]
Default:
Lev.5