REVO RT
from 35A to 90A
User’s manual
47
10.5 Digital Relay Outputs
P219 - Relay function 1 DO1 (Address ModBus 2219)
P221 - Relay function 2 DO2 (Address ModBus 2221)
P223 - Relay function 3 DO3 (Address ModBus 2223)
P225 - Relay function 4 DO4 (Address ModBus 2225)
P227 - Relay function 5 DO5 (Address ModBus 2227)
Various functions can be combined with the relay outputs by raising or lowering the relevant bit.
If I enable 2 functions, I will obtain the result of OR logic
Example: if bit 3 (Alarm1) and bit 4 (Alarm2) on DO1 are raised, this output will be active if Alarm1 or Alarm2 is active.
Functions associated with the output relay (DO):
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Function
Cooling Loop 1
Cooling Loop 2
Cooling Loop 3
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Heater Break
RS485 Watch dog
Probe error
Status DI 1
RUN Loop 1
RUN Loop 2
RUN Loop 3
Remote 1
Remote 2
Default:
0
P220 - Alarm contact type DO1 (Address ModBus 2220)
P222 - Alarm contact type DO2 (Address ModBus 2222)
P224 - Alarm contact type DO3 (Address ModBus 2224)
P226 - Alarm contact type DO4 (Address ModBus 2226)
P228 - Alarm contact type DO5 (Address ModBus 2228)
Alarm output contact 5 and trip type
0
1
n.o.
n.c.
(N.O.) Normally open (
Default
)
(N.C.) Normally closed