REVO RT
from 35A to 90A
User’s manual
19
Installation
Before to install, make sure that the Thyristor unit have not damages.
If the product has a fault, please contact the dealer from which you
purchased the product. Verify that the product is the same thing as
ordered.
The Thyristor unit must be always mounted in vertical position to
improve air cooling on heat-sink.
Maintain the minimum distances (
*
) in vertical and in horizontal
as represented,
this area must be free from obstacle
(wire, copper
bar, plastic channel).
When more unit has mounted inside the cabinet maintain the air
circulation like represented in figure without obstacle for the air flow.
Is necessary to install a fan to have better air circulation as calculated
previously.
6
The V Air flow must be equal or more than the value calculated.
If the cabinet fan mounted by the customer have an air flow lower than the correct value the warranty
will decay.
*
30 cm
*
20 cm
*
2 cm
AIR FLOW IN (V)
AIR FLOW OUT (V)
FAN
in aspiration
Air Grid
Содержание REVO RT
Страница 2: ......