REVO RT
from 35A to 90A
User’s manual
51
10.9 Serial RS485 MODBUS RTU
P300 - Slave Address (Address ModBus 2300)
Selects the slave address for serial communication
1 ÷ 254.
Default: 247
P301 - Baud Rate (Address ModBus 2301)
Selects the baud rate for serial communication
0
1
2
3
4
5
6
7
8
1200 bit/s
2400 bit/s
4800 bit/s
9600 bit/s
19200 bit/s (
Default
)
28800 bit/s
38400 bit/s
57600 bit/s
115200 bit/s
P302 - Serial Port Parameters (Address ModBus 2302)
Selects the format for Modbus RTU serial communication
0
1
2
3
4
5
8 bit, no parity, 1 stop bit (
Default
)
8 bit, even parity, 1 stop bit
8 bit, odd parity, 1 stop bit
8 bit, no parity, 2 stop bit
8 bit, even parity, 2 stop bit
8 bit, odd parity, 2 stop bit
P303 - Serial Delay (Address ModBus 2303)
Select serial delay
0 ÷ 100 ms.
Default: 5 ms.
P304 - RS458 MODBUS RTU WatchDog (Address ModBus 2304)
Selects the WatchDog time. If there is no serial communication within the set time, the controller switches
off the control output
0 Disabled offline (
Default
)
0.1-600.0 tenths of a second.
Содержание REVO RT
Страница 2: ......