16
REVEX
1PH from 30A to 40A
User’s manual
Technical Specifications
6.1 General features
Cover and Socket material:
PolymericV2
Mounting:
DIN bar (thickness type 1mm Max)
Utilization Category:
AC-51 AC-55b AC-56A
IP Code:
20
Method of Connecting:
Single Phase load
Auxiliary voltage, power supply Control Circuit:
24Vdc 500mA
Relay output for Heater Break Alarm
0.5A a 24Vac/dc
(only with HB option)
6.2 Input features
Digital Input:
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc) 5Hz max
Volt Analogic input:
0 ÷ 10Vdc impedance 15 kΩ
Current Analogic input:
4 ÷ 20mA impedance 100 Ω
Potentiometer:
10 kΩ min.
Logic input SSR (Fast Enable):
4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
3Hz Max duty cycle min. 100 ms
6.3 Output features (power device)
Nominal current in continuous service:
See order code
Max peak current (10ms)
540A for unit type 030
540A for unit type 035
700A for unit type 040
Nominal Voltage range
Ue
: 24÷600V
Repetitive peak reverse voltage
Uimp
:
1200V (480V) 1600V (600V)
Latching current:
250mA
Leakage current:
15mA eff
Frequency range:
47÷70Hz
Power loss (I=Inom):
38W for unit type 030
44W for unit type 035
50W for unit type 040
Isolation Voltage
Ui
: 2500Vac
6.4 Environmental installation conditions
Ambient temperature
0-40°C (32-104°F) at nominal current. Over 40°C-104°F use
the derating curve (max 50°C).
Storage temperature
-25°C to 70°C -13°F to 158°F
Installation place
Don’t install at direct sun light, where there are conductive
dust, corrosive gas, vibration or water and also in salty
environmental.
Altitude
Up to 1000 meter over sea level. For higher altitude reduce
the nominal current of 2% for each 100m over 1000m
Humidity
From 5 to 95% without condense and ice
Pollution Level
Up to 2nd Level ref. IEC 60947-1 6.1.3.2
6