Using the Configurator
Confi gurator software can be used like an alternative of the power controller’s keypad and set the advanced
features not available via the power controller’s onboard user interface.
Here we explain how to use it.
10.1 Typical Uses
The software may be used during commissioning to:
•
set internal parameter do determine how the power controller operates and performs;
•
save and restore a setup, copy or clone one power controller to another;
•
on a day-to-day basis to monitor operation and power usage;
•
examine performance in more detail to determine if any corrective actions are needed.
10.2 Communicating with Power Controllers
When commissioning the power controller, may be useful to connect a computer via the USB port, located
below the control panel’s display, so it’s possible to confi gure and examine the settings of the controller.
The controller’s electronics is powered vis USB cable, so it’s to possible to inspect it before applying power.
NOTE!
the power of the USB port is limited and not designed to power industrial cards, so it manages
to feed only the essential parts of the electronics. For complete control, you need to power up the
auxiliaries of the power controller.
10.3 Recipes
A recipe is a fi le that store the settings of power controller’s internal parameter.
It is used to save a power controller confi guration or to restore an existing confi guration in a power controller.
10.3.1 Upload a recipe
A recipe is created using upload function in the Confi gurator software and saving it as a fi le on the computer.
10.3.2 Download a recipe
An existing recipe can be downloaded to a power controller using download function in Confi gurator software.
10.4 How To
Here the procedures for common tasks are described step-by-step.
10.4.1 Install and communication with the power controller
Procedure to install the Confi gurator:
1) Locate the installer:
- On
https://www.cdautomation.com/
download/cd-automation/software/
ThyristorConfi gurator_ver6.exe
link is
possible Download it
- On the Controls Tools DVD ROM disk.
2) Double-click on the installer program to start
installation.
3) Follow the on-screen instructions.
10
Procedure to communicate with a power controller:
1)
if used direct USB connection:
- Connect the USB cable between
the computer and the micro USB
connector on the power controller’s
keypad
- if necessary, wait for the USB driver to
install.
2)
if used RS-485 connection
connect the
power
controller terminal to computer
RS485 port. Usually the standard pc do
not have a RS485 port so a USB-to-485
converter is required.
3) Launch the Confi gurator software and
select
-
REVEX 1PH:
for single phase
-
REVEX 2/3PH:
for 2 or 3 phase power
controller
4) Choose
Serial Port
From
Setting ->
Serial Port
menu
5) In value
Port
, select the COM port connected to the power
controller (see the note below)
6) To verify communications, click
Test
7) Click
OK
NOTE!
to determine which port is connected to the
power controller, you can:
•
in the Windows¨ Device Manager, under Ports (COM &
LPT), looking for the COM port named “LPC USB VCOM
Port (COMx)” where x is the port number
•
On confi gurator software:
- open the software without connect the unit and see the
available COM port on COM port window setting,
- close the COM setting window,
- connect the USB cable to the power controller (wait for
the USB driver to install if necessary),- open the COM
setting window, see the added COM number and select
it.