38
REVEX
1PH from 30A to 40A
User’s manual
9.4.6 Monitoring Menu
This section describes each item on the monitoring menu. Use this menu to view the states of digital input,
values of analog input and information about the power controller such as serial number and software version.
The password to access this menu is 0.
Parameter Name
Description
Modbus
Address
Par.
Type
Dig In 1
Indicate the state of the signal to digital input 1
13 bit8
Read
Only
Option
Value
Off
0
On
1
Parameter Name
Description
Modbus
Address
Par.
Type
Dig In 2
Indicate the state of the signal to digital input 2
13 bit9
Read
Only
Option
Value
Off
0
On
1
Parameter Name
Description
Modbus
Address
Par.
Type
Enable
Indicate whether or not the power controller is enabled.
The enable signal must be on for the unit to output power
to the load
14 bit2
Read
Only
Option
Value
Off
0
On
1
Parameter Name
Description
Modbus
Address
Par.
Type
SP Source
Indicate whether the power controller is local or remote set
point mode
14 bit1
Read
Only
Option
Description
Value
Local / Comms
Set Point via keypad or communication
2
Remote
Set Point via analog input
0
Содержание REVEX 1PH
Страница 2: ......