REVEX
1PH from 30A to 40A
User’s manual
27
9.2 Led indicators
The four indicators on the control panel show the general state of the power controller.
Aux High
SP 100%
1
Local/Remote
Flashing
Power output set locally or via
communications
Off
Power output set remotely (via
analog input)
2
Enable
On
Output enabled
Off
Output disabled
3
Communications
Flashing Active communications
4
Alarm
Flashing Active alarm
Off
No alarm
9.3 Displayed alarms
Control Panel Display and Keys are Not present for Option Codes: 2/3/4/D (see table pag. 15)
Alarm or
Message
Description
HeatBrk
Heater Break
(if available)
Aux High
Aux voltage too high
Aux Low
Aux voltage too low
BakeOut
Heater Bakeout function active
ComError
Communication Watchdog error
Aux Line Loss
Auxiliary voltage (24V) not present
Line Loss
Line power not detected
I Limit
Output limited by current limit feature (only single phase)
(if available)
SHRT
Short Circuit on SCR
If you have the version without display, all the functions shown on the display can be viewed via
the configurator
with display
Option code
0/6/7/9
on digit 12
In the version without display, Led 4 lit indicates that one of
the alarms shown in the table below is active. Connect the
configurator and check on the Test page which alarm is active.
without display
Option code:
2/3/4/D
on digit 12