32
REVEX
1PH from 30A to 40A
User’s manual
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Feedback
Choose the feed-back type
1
19
Read
Write
Option
Description
Value
V²
Voltage squared
0
None
No feed-back
1
I²
Current squared
2
Voltage
Voltage
32
Current
Current
64
Power
Power
128
External
External signal via analog input 2
256
DEFAULT:
None
1
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Pb Power
Set the gain for the main loop. A larger
value yields a larger adjustment for a
given deviation
10%
0 to 255
%
26
Read
Write
Ti Power
Set how aggressively the integral part
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
50
0 to 255
27
Read
Write
Pb Current
Set the gain for the current loop. A
larger value yields a larger adjustment
for a given deviation
10%
0 to 255
%
63
Read
Write
Ti Current
Set how aggressively the integral acts
in the current loop. A larger settings
yields a larger adjustment for a given
deviation over a given time
50
0 to 255
64
Read
Write
HB Sense
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
100%
0 to 100.0
%
29
Read
Write
Содержание REVEX 1PH
Страница 2: ......