![Carrier WeatherMaker 48TC 04 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/carrier/weathermaker-48tc-04/weathermaker-48tc-04_installation-instructions-manual_2560312060.webp)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480180-01
Printed in U.S.A.
Form 48TC-4-7-04SI
Pg CL-2
5-18A 4-18
Replaces: 48TC-4-7-03SI
© Carrier Corporation 2018
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
- -
-
- -
-
- -
-
- -
-
- -
- -
-
--
- -
-
- -
- -
-
- -
-
- -
-
- -
- - -
CUT ALON
G
DOTT
E
D
LINE
CU
T ALONG DOTTED LINE
PRESSURES
Gas Inlet Pressure _____________ in. wg
Gas Manifold Pressure
STAGE 1 _____________ in. wg
STAGE 2 _____________ in. wg
Refrigerant Suction
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge Using Charging Charts
(Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____
Verify smoke detector unit shutdown by utilizing magnet test
(Y/N) _____
III. HUMIDI-MIZER
®
START-UP (48TC*B07 ONLY)
STEPS
1. Check CTB for jumper 5, 6, 7 (Jumper 5, 6, 7 must be cut and open)
(Y/N) _____
2. Open humidistat contacts
(Y/N) _____
3. Start unit In cooling (Close Y1)
(Y/N) _____
OBSERVE AND RECORD
A. Suction pressure
_______________ PSIG
B. Discharge pressure
_______________ PSIG
C. Entering air temperature
_______________ °F
D. Liquid line temperature at outlet or reheat coil
_______________ °F
E. Confirm correct rotation for compressor
(Y/N) _____
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms
(Y/N) _____
4. Check unit charge per charging chart
(Y/N) _____
(Jumper 32L Motormaster
®
temperature sensor during this check. Remove jumper when complete.)
5. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed
(Y/N) _____
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected)
(Y/N) _____
B. Discharge pressure unchanged (Limited by Motormaster)
(Y/N) _____
C. Liquid temperature drops to 50 to 55 F range
(Y/N) _____
D. LSV solenoid energized (valve closes)
(Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. suction pressure increases to normal cooling level
B. discharge pressure decreases (35 to 50 psi)
C. liquid temperature returns to normal cooling level
D. LSV solenoid energized (valve closes)
E. DSV solenoid energized, valve opens
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8. Open W1 restore unit to dehumid mode
(Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
10. Restore set-points for thermostat and humidistat
(Y/N) _____
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...