25
Table 11 — HH57AC081 Sensor Wiring
Terminations
Use Fig. 39 and Table 12 to set the DIP switches for the
desired use of the sensor.
Table 12 — HH57AC081 Sensor DIP Switch
NOTE: When a S-bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60-minute setup period, no alarms for sensor
failures (except SAT) will be issued and no economizing func-
tion will be available.
CO
2
Sensor Wiring — When using a CO
2
sensor the black
and brown common wires are internally connected and only
one is connected to “IAQ COM” on the W7220. Use the power
from the W7220 to power the CO
2
sensor OR make sure the
ground for the power supplies are common. See Fig. 40 for
CO
2
sensor wiring.
Fig. 40 — CO
2
Sensor Wiring
INTERFACE OVERVIEW — This section describes how to
use the Economizer’s user interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface — The user interface consists of a 2-line LCD
display and a 4-button keypad on the front of the economizer
controller.
Keypad — The four navigation buttons (see Fig. 41) are used
to scroll through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Fig. 41 — W7220 Controller Button Description
To use the keypad when working with menus:
• Press the
▲
(Up arrow) button to move to the previous
menu.
• Press the
▼
(Down arrow) button to move to the next
menu.
• Press the
(Enter) button to display the first item in
the currently displayed menu.
• Press the
(Menu Up/Exit) button to exit a menu’s
item and return to the list of menus.
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the
(Enter) button to display the first item in the
currently displayed menu.
3. Use the
▲
and
▼
buttons to scroll to the desired parame-
ter.
4. Press the
(Enter) button to display the value of the
currently displayed item.
5. Press the
▲
button to increase (change) the displayed pa-
rameter value.
6. Press the
▼
button to decrease (change) the displayed pa-
rameter value.
NOTE: When values are displayed, pressing and holding the
or button causes the display to automatically increment.
7. Press the
(Enter) button to accept the displayed value
and store it in nonvolatile RAM. “CHANGE STORED”
displays.
8. Press the
(Enter) button to return to the current menu
parameter.
9. Press the
(Menu Up/Exit) button to return to the pre-
vious menu.
Menu Structure — Table 13 illustrates the complete hierarchy
of menus and parameters for the EconoMi$er
®
X system.
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
TERMINAL
TYPE
DESCRIPTION
NUMBER
LABEL
1
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
2
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
USE
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1
2
3
DA
OFF
ON
OFF
RA
ON
OFF
OFF
OA
OFF
OFF
OFF
CO
2
SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...