Table 13 — Menu Structure (cont)
LEGEND
NOTES:
1.
Table 13 illustrates the complete hierarchy. Your menu parameters may
be different depending on your configuration. For example if you do not
have a DCV (CO
2
) sensor, then none of the DCV parameters appear.
2.
When values are displayed, pressing and holding the
or
button
causes the display to automatically increment.
3.
ERV Operation: When in cooling mode AND the conditions are NOT OK
for economizing - the ERV terminal will be energized. In the Heating mode,
the ERV terminal will be energized when the OA is below the ERV OAT
setpoint in the setpoint menu.
4.
STATUS —> OCCUPIED — The factory-standard Occupancy signal origi-
nates with a thermostat or other controller call for indoor fan operation at
CTB terminal G. This signal passes through the Central Terminal Board’s
OCCUPIED jumper JMP1 to the ECONO connector and to the W7220’s
OCC input terminal. An external timeclock or relay is required to implement
an Occupancy schedule on the economizer damper position.
5.
STATUS —> MA TEMP, SETPOINTS —> MAT SET — The W7220 menu
parameters and labels include designations MA, MAT and Mixed Air for the
economizer cooling control sensor. On these rooftop units, the economizer
control sensor is located downstream of the evaporator/indoor coil in the
supply fan section where this sensor is designated as Supply Air Tempera-
ture (SAT) sensor.
6.
SETPOINTS —> DRYBLB SET — This point is not displayed if a Return
Air (differential) temperature sensor or an Outdoor Air enthalpy sensor is
connected.
7.
SYSTEM SETUP parameters must be configured as noted for 2-Speed
unit operation:
EQUIPMENT = CONV
AUX2 I = W
FAN TYPE = 2SPEED
MENU
PARAMETER
PARAMETER
DEFAULT
VALUE
PARAMETER
RANGE AND
INCREMENT
NOTES
ALARMS
(CONT)
SHUTDOWN ACTIVE
N/A
N/A
AUX2 IN is programmed for SHUTDOWN and 24 V has been applied to
AUX 2IN terminal.
DMP CAL RUNNING
N/A
N/A
DAMPER CALIBRATION ROUTINE RUNNING
If DCV Auto enable has been programmed, when the W7220 is complet-
ing a calibration on the dampers, this alarm will display. Wait until the
calibration is completed and the alarm will go away. Must have OA, MA
and RA sensors for DCV calibration; set up in the Advanced setup
menu.
DA SENS ALM
N/A
N/A
DISCHARGE AIR TEMPERATURE SENSOR ALARM
Discharge air temperature is out of the range set in the ADVANCED
SETUP Menu. Check the temperature of the discharge air.
SYS ALARM
N/A
N/A
When AUX1-0 is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1-0 terminal has 24 Vac out.
ACT UNDER V
N/A
N/A
ACTUATOR VOLTAGE LOW
Voltage received by actuator is above expected range.
ACT OVER V
N/A
N/A
ACTUATOR VOLTAGE HIGH
Voltage received by actuator is below expected range.
ACT STALLED
N/A
N/A
ACTUATOR STALLED
Actuator stopped before achieving commanded position.
CLO
—
Compressor Lockout
DCV
—
Demand Controlled Ventilation
ERV
—
Energy Recovery Ventilator
LCD
—
Liquid Crystal Display
MA
—
Mixed Air
MAT
—
Mixed Air Temperature
N/A
—
Not Applicable
OA
—
Outdoor Air
OAT
—
Outdoor Air Temperature
OCC
—
Occupied
RA
—
Return Air
RAT
—
Return Air Temperature
RTU
—
Rooftop Unit
SYS
—
System
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...