Table 30 — RTU Open Controller Inputs and Outputs
LEGEND
1.
Safety Chain Feedback: 24Vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instructions.
2.
These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Sec-
tion for wiring and setup instructions.
3.
Parallel pins J5–1 = J2–6, J5–3 = J1–10, J5–5 = J1–2 are used for field installation.
4.
Refer to the input configuration and accessory sections of the RTU Open Multi–Protocol Controller Controls, Start–Up, Operation and Troubleshoot-
ing manual for more detail.
POINT NAME
BACNET OBJECT
NAME
TYPE OF I/O
CONNECTION
PIN NUMBER (S)
CHANNEL DESIGNATION
DEDICATED INPUTS
Space Temp / Zone Temp
zone_temp
AI (10K Thermistor)
J20–1 & 2
Analog Input 10
Supply Air Temperature
sa_temp
AI (10K Thermistor)
J2–1 & 2
Analog Input 6
Outside Air Temperature
oa_temp
AI (10K Thermistor)
J2–3 & 4
Analog Input 7
Space Temperature Offset Pot
stpt_adj_offset
AI(100K
Potentiometer)
J20–3 & 4
Analog Input 11
Safety Chain Feedback
safety_status
BI (24 VAC)
J1–9
Binary Input 4
Compressor Safety Status
1
comp_status
BI (24 VAC)
J1–2
Binary Input 3
Fire Shutdown Status
firedown_status
BI (24 VAC)
J1–10
Binary Input 5
Enthalpy Status
enthalpy_status
BI (24 VAC)
J2–6 & 7
Binary Input 8
Humidistat Input Status
humstat_status
BI (24 VAC)
J5–7 & 8
Binary Input 9
Zone Temperature
n/a
n/a
J13–1–4
Rnet
CONFIGURABLE INPUTS
4
Indoor Air CO
2
iaq
AI (4–20 mA)
J4–2 & 3 or J4–5
& 6
Analog Input 2
Outdoor Air CO
2
oaq
AI (4–20 mA)
Analog Input 1
Space Relative Humidity
space_rh
AI (4–20 mA)
Analog Input 10
Supply Fan Status
2
sfan_status
BI (24 VAC)
J5–1 & 2 or
J5–3 & 4, J5–5 &
6 or J5–7 & 8
3
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Filter Status
2
filter_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Door Contact
2
door_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
Remote Occupancy Input
2
occ_contact_status
BI (24 VAC)
Binary Input 3, 5, 8, or 9, except where
intrinsic input is used
IGC Input
2
igcovr_status
BI (24 VAC)
Binary Input 9. Mandatory input on gas
heat units.
OUTPUTS
Economizer Output
econ_output
AO (4–20mA)
J2–5
Analog Output 1
Supply Fan VFD
vfd_output
AO (2–10Vdc)
J22–1 & 2
Analog Output 2
Supply Fan Relay
sfan
BO Relay
(24VAC, 1A)
J1–4
Binary Output 1 (G)
Cool 1 Relay State
comp_1
BO Relay
(24VAC, 1A)
J1–8
Binary Output 5 (Y1)
Cool 2 Relay State
comp_2
BO Relay
(24VAC, 1A)
J1–7
Binary Output 4 (Y2)
Cool 3 Relay State
comp_3
BO Relay
(24VAC, 1A)
J11–5 & 6
Binary Output 7 (Y3)
Heat 1 Relay State
heat_1
BO Relay
(24VAC, 1A)
J1–6
Binary Output 3 (W1)
Heat 2 Relay State
heat_2
BO Relay
(24VAC, 1A)
J1–5
Binary Output 2 (W2)
Power Exhaust Relay State
pexh
BO Relay
(24VAC, 1A)
J11–2 & 3
(N.O.)
Binary Output 8 (PE)
Dehumidification Relay
dehum
BO Relay
(24VAC, 1A)
J11–7 & 8
(N.O.)
Binary Output 6
AI
— Analog Input
AO
— Analog Output
BI
— Binary Input
BO
— Binary Output
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...