Table 19 — Dry Bulb Operation No DCV (CO
2
Sensor) — 2 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I
and Y2–I have not been satisfied.
Table 20 — Dry Bulb Operation with DCV (CO
2
Sensor) — 2 Speed Fan
*With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2–O after the delay if the call for Y1–I
and Y2–I have not been satisfied.
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NONE
NO
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
NONE
YES
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
0v/Off
0v/Off
MIN POS to Full
Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
MIN POS to Full
Open
Closed to Full-Open
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
Above CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off*
VENTMIN to
Full-Open
Closed to Full-Open
Содержание WeatherMaker 48TC 04
Страница 4: ...4 Fig 2 Unit Dimensional Drawing ...
Страница 5: ...5 Fig 2 Unit Dimensional Drawing cont ...
Страница 21: ...21 Fig 34 48TC B07 Unit with Humidi MiZer Adaptive Dehumidification System Humidistat Wiring ...
Страница 39: ...39 Fig 45 PremierLink Wiring Schematic ...
Страница 40: ...40 Fig 46 PremierLink Wiring Schematic with Humidi MiZer System ...
Страница 48: ...48 Fig 65 Typical RTU Open System Control Wiring Diagram ...
Страница 49: ...49 Fig 66 Typical RTU Open System Control Wiring Diagram with Humidi MiZer System ...