UC Open XP IO Installation 

 

 

20 

UC Open XP/UC Open XP IO 

 

Set the UC Open XP IO's address on the rotary switch. For example, the switch below shows an address 

of 1. 

 

NOTE

  Do not change the address from the default setting of 1! 

Turn on the UC Open XP IO's power, then turn on the attached UC Open XP's power. TheUC Open XP 

reads the powered UC Open XP IO's address each time you turn on the UC Open XP. 

  
 

 

Wiring inputs and outputs 

See 

Appendix A

 (page 29) to print a blank wire list.  

 

Input wiring specifications 

 

Input

 

Maximum length

 

Minimum gauge

 

Shielding 

0–5 Vdc 

500 feet 

(152 meters) 

 

22 AWG 

100 feet Unshielded 
100 - 500 feet Shielded 

Thermistor 
Dry contact 
Pulse counter 

TLO 

500 feet 

(152 meters) 

 

22 AWG 

100 feet Unshielded 
100 - 500 feet Shielded 

  
 

 

Inputs UC Open XP IO 

The UC Open XP IO has 16 inputs that accept the following signal types: 
  

Signal Type  

Description 

Thermistor 

Precon type 2 (10 kOhm at 77°F). Input voltages should be from 0.489 Vdc 

to 3.825 Vdc for thermistors. 

Dry contact 

A 5 Vdc wetting voltage detects contact position, resulting in a 1 mA 

maximum sense current when the contacts are closed. 

0–5 Vdc 

 

The output impedance of a 0–5 Vdc or a 0–10 Vdc source must not exceed 

200 Ohms. The input impedance of the UC Open XP is approximately 20 

kOhm. 

Pulse counter* 

10 pulses per second max. Minimum pulse width (on or off time) required for 

each pulse is 50 msec. 

  

Содержание UC Open XP

Страница 1: ...e en n X XP P I IO O I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol...

Страница 2: ......

Страница 3: ...ount the UC Open XP IO 18 To wire for power 19 To set UC Open XP IO s address 19 Wiring inputs and outputs 20 Input wiring specifications 20 Inputs UC Open XP IO 20 Binary outputs 21 To wire inputs an...

Страница 4: ...Table of Contents ii UC Open XP UC Open XP IO FCC Compliance 37 CE Compliance 37 BACnet Compliance 37...

Страница 5: ...4 Vac 10 50 60 Hz 20 VA power consumption 26 VA with BACview attached 26 Vdc 25 V min 30 V max Single Class 2 source only 100 VA or less BACnet Port Port 2a BACnet MS TP 9600 bps 19 2 kbps 38 4 kbps o...

Страница 6: ...minimum of 10 000 hours of data retention during power outages Protection Incoming power and network connections are protected by non replaceable internal solid state polyswitches that reset themselv...

Страница 7: ...0 2 cm 1 2 in 1 3 cm 13 64 in 5 cm Panel depth 2 in 5 1 cm Weight 1 1lb 0 5 kg BACnet support Conforms to the Advanced Application Controller B AAC Standard Device Profile as defined in ANSI ASHRAE St...

Страница 8: ...Introduction 4 UC Open XP UC Open XP IO...

Страница 9: ...inary outputs configured as dry contact normally open and must be powered from a Class 2 power source Protection Incoming power and network connections are protected by non replaceable internal solid...

Страница 10: ...dimensions A B 10 5 8 in 27 0 cm 3 in 7 6 cm Mounting dimensions C D E 10 3 16 in 25 9 cm 1 1 2 in 3 8 cm 13 64 in 5 cm Panel depth 1 1 2 in 8 cm Weight 73 lbs 33 kg Listed by UL 916 Canadian Std C22...

Страница 11: ...XP UC Open XP IO 7 Safety considerations Disconnect electrical power to the UC Open XP before wiring it Failure to follow this warning could cause electrical shock personal injury or damage to the con...

Страница 12: ...under Reports in Field Assistant after installing your control program UC Open XP Installation Guide 1 Prepare a wire list using the points list Refer to the Appendix page 29 2 Use the wire list and t...

Страница 13: ...llation and Start up Guide 5 Check out and commission the equipment To mount the UC Open XP When you handle the UC Open XP Do not contaminate the printed circuit board with fingerprints moisture or an...

Страница 14: ...es to the screw terminal connector 5 Apply primary power to the transformer 6 Measure the voltage at the UC Open XP s power screw terminal connector to verify that the voltage is within the operating...

Страница 15: ...UC Open XP Wiring the UC Open XP to the MS TP network The UC Open XP communicates using BACnet on an MS TP network segment communications at 9600 bps 19 2 kbps 38 4 kbps or 76 8 kbps Wire the control...

Страница 16: ...hout the network segment 4 Verify that the MSTP jumper is set to MSTP 5 Set DIP switches 1 and 2 to the appropriate baud rate See the MSTP baud diagram on the UC Open XP The default baud rate is 76 8...

Страница 17: ...elded 100 500 feet Shielded RTD 100 feet 30 meters 22 AWG Shielded SPT sensors 500 feet 152 meters 18 AWG Unshielded Inputs UC Open XP The UC Open XP has 12 inputs that accept the signal types describ...

Страница 18: ...twice the cable length Acceptable voltage drop in the wire from the controller to the controlled device Resistance Ohms of the chosen wire gauge Maximum current Amps the controlled device requires to...

Страница 19: ...e at the sensor end Connect the shield wire to the GND terminal with the ground wire Use only UI 1 or UI 2 for pulse counter or timed local override For an internally powered 4 20 mA sensor wire the s...

Страница 20: ...act 0 5 Vdc 0 10 Vdc 0 20 mA RTD Set each input s Universal Input Mode Select jumper to the type of signal the input will receive Aux Power Out port Internally powered 4 20 mA Set the Select jumper to...

Страница 21: ...17 5 Connect the analog output wiring to the screw terminals on the UC Open XP and to the controlled device 6 Set the AO Mode Select jumper to the type of device you are wiring the output to 7 Turn o...

Страница 22: ...re or any foreign material Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Wiring restrictions...

Страница 23: ...are present For the UC Open XP to recognize an attached expander you must turn on the expander before you turn on the UC Open XP 1 Turn off the UC Open XP IO s power jumper 2 Connect the input wiring...

Страница 24: ...AWG 100 feet Unshielded 100 500 feet Shielded Thermistor Dry contact Pulse counter TLO 500 feet 152 meters 22 AWG 100 feet Unshielded 100 500 feet Shielded Inputs UC Open XP IO The UC Open XP IO has...

Страница 25: ...ual wire For 2 conductor wires this is twice the cable length Acceptable voltage drop in the wire from the expander to the controlled device Resistance Ohms of the chosen wire gauge Maximum current Am...

Страница 26: ...jumper to indicate the type of input WARNING Do not apply 24 Vac to these universal inputs 5 Connect binary output wiring to the BO screw terminals on the UC Open XP IO and to the controlled device 6...

Страница 27: ...t INFO button to cycle through zone and outdoor air temperatures setpoints and local override time MODE button to cycle through custom programmed modes FAN SPEED button to adjust fan speed Local acces...

Страница 28: ...and pull off the outer jacket of the Rnet cable s Do not nick the inner insulation Strip about 25 inch 6 cm of the inner insulation from each wire Outer Jacket Inner insulation 25 in 6 cm 2 Wire each...

Страница 29: ...s For BACview6 Handheld keypad display unit Local Access port Temporary user interface for driver parameter access Virtual BACview software running on a laptop Local Access port Temporary user interfa...

Страница 30: ...s when the controller receives data from the network segment there is an Rx LED for Ports 1 and 2 Tx Lights when the controller transits data from the network segment there is an Rx LED for Ports 1 an...

Страница 31: ...off then on Download memory to the UC Open XP Replace the UC Open XP Restore factory defaults CAUTION To erase volatile memory data and restore factory default configuration settings This erases all...

Страница 32: ...10 000 hours of data retention during power outages CAUTION Power must be ON to the UC Open XP when replacing the battery or your date time and trend data will be lost 1 Remove the battery from the co...

Страница 33: ...GND Point Cable Inputs G Input Type Jumper Position of Pins I O Sensor code Equipment Name Point Name 3 5 0 10 Upper UI 1 3 5 Pulse Other Middle 3 5 4 20 Lower 4 5 0 10 Upper UI 2 4 5 Pulse Other Mid...

Страница 34: ...ype Jumper Position of Pins I O Sensor code Equipment Name Point Name 1 2 mA Left 2 pins AO 1 Volt Right 2 pins 3 mA Left 2 pins AO 2 Volt Right 2 pins 5 6 0 10 N A AO 3 7 8 0 10 N A AO 4 9 10 0 10 N...

Страница 35: ...Jumper UI 9 1 2 Therm Dry Contact Jumper 3 4 0 5V No Jumper UI 10 3 4 Therm Dry Contact Jumper 5 6 0 5V No Jumper UI 11 5 6 Therm Dry Contact Jumper 7 8 0 5V No Jumper UI 12 7 8 Therm Dry Contact Jump...

Страница 36: ...endix A UC Open XP and UC Open XP IO wire lists 32 UC Open XP UC Open XP IO 7 8 N O N A BO 4 9 10 N O N A BO 5 11 12 N O N A BO 6 13 14 N O N A BO 7 15 16 N O N A BO 8 NOTE All inputs can be pulse inp...

Страница 37: ...5 17 Duct Static Pressure 4 20mA transmitter Lower UI 10 AI 16 17 Indoor Air Quality CO2 4 20mA transmitter Lower UI 11 AI 18 20 Outdoor Air Quality CO2 4 20mA transmitter Lower UI 12 AI 19 20 Buildin...

Страница 38: ...n PRESS Dry Contact Middle BI 6 BI 11 12 Smoke Purge PURGE Dry Contact Middle BI 7 BI 13 14 Enthaply Switch Input Dry Contact Middle BI 8 UI 9 AI 1 2 Preheat Coil Temp 10K Thermistor Middle UI 10 UI 1...

Страница 39: ...UI 7 AI 12 14 Return Air Temp 10K Thermistor Middle UI 8 AI 13 14 Space RH 4 20mA transmitter Lower UI 9 N A UI 10 AI 16 17 Indoor Air Quality CO2 4 20mA transmitter Lower UI 11 AI 18 20 Outdoor Air...

Страница 40: ...ation PRESS Dry Contact Middle BI 6 BI 11 12 Smoke Purge PURGE Dry Contact Middle BI 7 BI 13 14 Enthaply Switch Input Dry Contact Middle BI 8 UI 9 AI 1 2 Preheat Coil Temp 10K Thermistor Middle UI 10...

Страница 41: ...cause harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for c...

Страница 42: ......

Страница 43: ......

Страница 44: ...CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 437 01 11 19 2010...

Отзывы: