Appendix B: AHU VAV input and output points list
34
UC Open XP/UC Open XP IO
AHU VAV inputs and outputs on the UC Open XP IO
I/O
Type
Input
Terminal
Gnd
Terminal
Point Name/
Function
Hardware/
Signal
Jumper
position of
terminals
BI-1
BI
1
2
Return/Exhaust Fan Status
Dry Contact
Middle
BI-2
BI
3
4
High Duct RH
Dry Contact
Middle
BI-3
BI
5
6
Fire Shutdown - FSD
Dry Contact
Middle
BI-4
BI
7
8
Smoke Evacuation- EVAC
Dry Contact
Middle
BI-5
BI
9
10
Smoke Pressurization - PRESS
Dry Contact
Middle
BI-6
BI
11
12
Smoke Purge - PURGE
Dry Contact
Middle
BI-7
BI
13
14
Enthaply Switch Input
Dry Contact
Middle
BI-8
UI-9
AI
1
2
Preheat Coil Temp
10K Thermistor
Middle
UI-10
UI-11
UI-12
UI-13
UI-14
UI-15
UI-16
BI
15
16
Filter Status 2
Relay
N/A
BO-1
BO
1
2
F&B 2 Pos Hot Water Valve
Relay
N/A
BO-2
BO
3
4
F&B 2 Pos Chilled Water Valve
Relay
N/A
BO-3
BO
5
6
DX Stage 4
Relay
N/A
BO-4
BO
7
8
DX Stage 5
Relay
N/A
BO-5
BO
9
10
DX Stage 6
Relay
N/A
BO-6
BO
11
12
Preheat 2 Pos Hot Water valve
Relay
N/A
BO-7
BO
13
14
Smoke Control K1
Relay
N/A
BO-8
BO
15
16
Smoke Control K2
Relay
N/A
Legend
UI
- Universal Input
BI
- Binary Input
BO
- Binary Output