UC Open XP/UC Open XP IO
33
These wire lists represent all the possible points for this application. The points that are actually used in your
application depend on the equipment options you select in ApplicationBuilder.
AHU VAV inputs and outputs on the UC Open XP
I/O
Type
I/O
Terminal
Gnd
Terminal
Point Name/
Function
Hardware/
Signal
Jumper
Position of
Pins
UI-1
BI
3
5
Filter Status 1
Dry Contact
Middle
UI-2
AI
4
5
Supply Air Temp/
Cold Deck Temp
10K Thermistor
Middle
UI-3
AI
6
8
Mixed Air Temp
10K Thermistor
Middle
UI-4
AI
7
8
Outdoor Air Temp
5K Thermistor
Middle
UI-5
BI
9
11
Freezestat
Dry Contact
Middle
UI-6
BI
10
11
Supply Fan Status
Dry Contact
Middle
UI-7
AI
12
14
Return Air Temp
10K Thermistor
Middle
UI-8
AI
13
14
Space RH
4-20mA transmitter
Lower
UI-9
AI
15
17
Duct Static Pressure
4-20mA transmitter
Lower
UI-10
AI
16
17
Indoor Air Quality (CO2)
4-20mA transmitter
Lower
UI-11
AI
18
20
Outdoor Air Quality (CO2)
4-20mA transmitter
Lower
UI-12
AI
19
20
Building Pressure
4-20mA transmitter
Lower
BO-1
BO
2
Supply Fan S/S
Relay
N/A
BO-2
BO
5
Humidifier Enable
Relay
N/A
BO-3
BO
8
Return/Exhaust Fan S/S
Relay
N/A
BO-4
BO
11
DX Stage 1
Relay
N/A
BO-5
BO
14
DX Stage 2
Relay
N/A
BO-6
BO
17
DX Stage 3
Relay
N/A
AO-1
AO
1
2
Modulating OA Damper
0-10 Volt
N/A
AO-2
AO
3
4
Modulating HW Valve/Electric
Heat Staging*
0-10 Volt
N/A
AO-3
AO
5
6
Modulating CW Valve/
F & B Damper
0-10 Volt
N/A
AO-4
AO
7
8
Supply Fan VFD
0-10 Volt
N/A
AO-5
AO
9
10
Return Fan VFD
0-10 Volt
N/A
AO-6
AO
11
12
Preheat Valve/FB Damper
0-10 Volt
N/A
Legend
AI
- Analog Input
AO
- Analog Output
BI
- Binary Input
BO
- Binary Output
* Electric Heat Staging AO is output to a Stage Sequencer
NOTE
Connect SPT sensor to the Rnet port.
Appendix B: AHU VAV input and output points list