UC Open XP installation
12
UC Open XP/UC Open XP IO
To wire the controller to the network
1
Pull the screw terminal connector from the controller's power terminals labeled
Gnd
and
24 Vac
or
Hot
.
2
Check the communications wiring for shorts and grounds.
3
Connect the communications wiring to the BACnet port’s screw terminals labeled
Net +
,
Net -
, and
Shield
.
NOTE
Use the same polarity throughout the network segment.
4
Verify that the
MSTP
jumper is set to
MSTP
.
5
Set DIP switches 1 and 2 to the appropriate baud rate. See the MSTP baud diagram on the UC Open XP.
The default baud rate is 76.8 kbps.
NOTE
Use the same baud rate for all controllers on the network segment.
6
Set DIP switches 3 and 4 for
MSTP
.
7
Verify the jumper is set on the right 2 pins.
8
Verify that the Communications Selection jumper is set to EIA-485.
9
Insert the power screw terminal connector into the UC Open XP's power terminals.
10
Verify communication with the network by viewing a module status report.