Wiring an SPT sensor
24
UC Open XP/UC Open XP IO
Recommended coloring
Jacket: White
Wiring: Black, white, green, red
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
To wire the SPT sensor to the controller
1
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)
2
Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
NOTE
Carrier recommends that you use the following Rnet wiring scheme:
Connect this wire...
Red
To this terminal...
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
SPT Sensor
G
ND
R
N
ET
+
GND
R
NE
T-
+
12V
Rnet
Rnet+
Rnet-
+12V