UC Open XP/UC Open XP IO
27
If Run LED shows...
And Error LED shows...
Status is...
2 flashes per second
On
Exec halted after frequent system
errors or control programs halted
5 flashes per second
On
Exec start-up aborted, Boot is
running
5 flashes per second
Off
Firmware transfer in progress,
Boot is running
7 flashes per second
7 flashes per second,
alternating with
Run
LED
Ten second recovery period after
brownout
14 flashes per second
14 flashes per second,
alternating with
Run
LED
Brownout
On
On
Failure. Try the following solutions:
•
Turn the UC Open XP off, then
on.
•
Download memory to the UC
Open XP.
•
Replace the UC Open XP.
Restore factory defaults
CAUTION!
To erase volatile memory data and restore factory default configuration settings:
This erases all archived information and user-configuration settings. You will have to
reconfigure all custom settings. It is recommended to restore the factory defaults only under the guidance
of Carrier Control Systems Support.
1
Turn off the UC Open XP's power switch.
2
Put the
Format
jumper on.
3
Turn on the UC Open XP's power switch.
4
Remove the format jumper.
Serial number
If you need the UC Open XP's serial number when troubleshooting, the number is on:
•
a sticker on the back of the main controller board
•
a Module Status report (modstat) from your user interface