28
Start-up delay
When changing the operating type (Local/Remote/Network),
the control normally undergoes the transition stage during
which the unit is stopped, and then allowed to start again
(start-up delay is applied).
Unit stop function
This function controls the unit compressor capacity reduction.
If there is an alarm or a demand to stop, it forces the
compressors to the minimum capacity before stopping them.
8 -
TOUCH PILOT CONTROL OPERATION
8.1 - Start / Stop control
The unit state is determined based on a number of factors,
including its operating type, active overrides, open contacts,
master/slave configuration, or alarms triggered due to
operating conditions.
The table given below summarises the unit control type
[ctrl_typ] and its running status with regard to the following
parameters:
• Operating type:
Operating type is selected using the
Start/Stop
button on the user interface.
LOFF
Local off
L-C
Local on
L-SC
Local schedule
Rem
Remote
Net
Network
Mast
Master unit
Active operating type
Parameters status
Control
type
Unit
state
LOFF
L-C
L-SC Rem
Net
Mast
Start/Stop
force
command
Remote
start/stop
contact
Master
control
type
Start/Stop
schedule
Network
Emergency
Shutdown
Alarm
shutdown
-
-
-
-
-
-
-
-
-
enabled
-
-
off
-
-
-
-
-
-
-
-
-
-
-
yes
-
off
active
-
-
-
-
-
-
-
-
-
-
-
local
off
-
-
active
-
-
-
-
-
-
unoccupied
-
-
local
off
-
-
-
active
-
-
-
open
-
-
-
-
remote
off
-
-
-
active
-
-
-
-
-
unoccupied
-
-
remote
off
-
-
-
-
active
-
disabled
-
-
-
-
-
network
off
-
-
-
-
active
-
-
-
-
unoccupied
-
-
network
off
-
-
-
-
-
active
-
-
local
unoccupied
-
-
local
off
-
-
-
-
-
active
-
open
remote
-
-
-
remote
off
-
-
-
-
-
active
-
-
remote unoccupied
-
-
remote
off
-
-
-
-
-
active
disabled
-
network
-
-
-
network
off
-
-
-
-
-
active
-
-
network unoccupied
-
-
network
off
-
active
-
-
-
-
-
-
-
-
disabled
no
local
on
-
-
active
-
-
-
-
-
-
occupied
disabled
no
local
on
-
-
-
active
-
-
-
closed
-
occupied
disabled
no
remote
on
-
-
-
-
active
-
enabled
-
-
occupied
disabled
no
network
on
-
-
-
-
-
active
-
-
local
occupied
disabled
no
local
on
-
-
-
-
-
active
-
closed
remote
occupied
disabled
no
remote
on
-
-
-
-
-
active
enabled
-
network
occupied
disabled
no
network
on
•
Start/stop force command [CHIL_S_S]:
Unit start/stop force command can be used to control
the unit state in the Network operating type.
Command set to stop:
The unit is halted.
Command set to start:
The unit runs according to
schedule 1.
•
Remote start/stop contact status [Onoff_sw]:
Start/stop contact can be used to control the unit state
in the Remote operating type.
•
Master control type [ms_ctrl]:
When the unit is the
master unit in a two-unit master/slave arrangement,
the master unit may be set to be controlled locally,
remotely or via network.
•
Start/stop schedule [chil_occ]:
Occupied or unoccupied
status of the unit.
•
Network emergency stop command [EMMSTOP]:
If activated, the unit shuts down regardless of the active
operating type.
• General alarm:
The unit shuts down due to failure.
IMPORTANT:
When the unit is stopping or there is a demand
to stop the unit, compressors are stopped consecutively.
In case of emergency stop, all compressors are stopped at
the same time.