20
Outputs Status Menu – OUTPUTS (continued)
No. Name
Status
Unit
Displayed text*
Description
6
ISO_OP_A
off/on
-
Ref Iso Valve Open A
Refrigerant isolation valve open, circuit A
7
ISO_POSA
close/open
-
Ref Iso Valve pos. A
Refrigerant isolation valve position, circuit A
8
OIL_HT_A
off/on
-
Oil Heater Output A
Oil heater output, circuit A
9
CP_B
off/on
-
Compressor B
Compressor B status
10
OIL_SL_B
off/on
-
Oil Solenoid Output B
Oil solenoid output, circuit B
11
CAPT010B
0 to 10
V
Capacity Signal Cir B
0-10V capacity signal, circuit B
12
VFAN_B
0 to 100
%
VariFan Speed B
Variable speed fan, circuit B
13
ISO_CL_B
off/on
-
Ref Iso Valve Close B
Refrigerant isolation valve closed, circuit B
14
ISO_OP_B
off/on
-
Ref Iso Valve Open B
Refrigerant isolation valve open, circuit B
15
ISO_POSB
close/open
-
Ref Iso Valve pos. B
Refrigerant isolation valve position, circuit B
16
OIL_HT_B
off/on
-
Oil Heater Output B
Oil heater output, circuit B
17
CAPT_010
0 to 10
V
Chiller Capacity signal
Chiller capacity signal
18
ALARM
off/on
-
Alarm Relay Status
Alarm relay status
on = at least one circuit is stopped because of the
existing alarm(s)
19
RUNNING
off/on
-
Running Relay Status
Running relay status
on = chiller (or at least one pump) is running
20
ALERT
off/on
-
Alert Relay State
Alert relay status
on = alarm that does not stop the circuit or the unit is
triggered
21
SHUTDOWN
off/on
-
Shutdown Indicator State
Shutdown indicator state
on = unit shuts down because of the existing alarm(s)
22
C_HEATER
off/on
-
Cooler Heater Output
Cooler heater output
23
ELECBFAN
off/on
-
Electrical box fan
Electrical box fan
24
ELEBFAN2
off/on
-
Electrical box fan 2
Electrical box fan 2
25
VI_CMP_A
off/on
-
VI compressor command A
Vi compressor control command A
26
VI_CMP_B
off/on
-
VI compressor command B
Vi compressor control command B
27
READY
off/on
-
Ready or Running Status
Ready or Running Status
on = chiller is running
off = chiller is stopped
28
WTANK_HT
off/on
-
Water Tank heater
Water Tank heater
*Depends on the selected language (English by default).
Pump Status Menu – PUMPSTAT
No. Name
Status
Unit
Displayed text*
Description
1
SET_FLOW
no/yes
-
Cooler Flow Setpoint Out
Evaporator flow setpoint output
2
CPUMP_1
off/on
-
Cooler Pump #1 Command
Evaporator pump 1 control enabled
3
CPUMP_2
off/on
-
Cooler Pump #2 Command
Evaporator pump 2 control enabled
4
ROTCPUMP
no/yes
-
Rotate Cooler Pumps ?
Evaporator pumps rotation
5
FLOW_SW
open/close
-
Cooler Flow Switch
Evaporator flow switch
6
VPMP_CMD
0 to 100
%
Variable speed pump cmd
Variable speed pump command
7
WAT_FLOW
-
l/s
Water flow (kit hydro)
Water flow (hydronic kit)
8
pmpStat
0 to 14
-
Pump Control Status
0 = Pump stopped
1 = Temp. delta control
2 = Pressure delta control
3 = Constant pressure control
4 = Fixed speed control
Override:
11 = Low water temperature
12 = Freeze protection
13 = Prevention of max flow
14 = Protection against max flow
*Depends on the selected language (English by default).