36
JBus
code
Alarm
code Description
Reset type
Action taken
Possible cause
34
4503
Loss of Communication with Auxiliary # 3
As above
Circuit B shuts down
As above
35
4504
Loss of Communication with Auxiliary # 4
As above
No action (alert)
As above
36
4603
Loss of communication with Energy
Management Board
As above
No action (alert)
As above
37
4701
Loss of Communication with VLT Drive
Board #1
As above
Circuit A shuts down
As above
38
4702
Loss of Communication with VLT Drive
Board #2
As above
Circuit B shuts down
As above
39
4704
Loss of Communication with Drive Board #4 As above
Circuit A shuts down
As above
40
4705
Loss of Communication with Drive Board #5 As above
Circuit A shuts down
As above
41
4706
Loss of Communication with Drive Board #6 As above
Circuit A shuts down
As above
42
4707
Loss of Communication with Drive Board #7 As above
Circuit B shuts down
As above
43
4708
Loss of Communication with Drive Board #8 As above
Circuit B shuts down
As above
44
4709
Loss of Communication with Drive Board #9 As above
Circuit B shuts down
As above
45
4710
Loss of Communication with Drive Board #10 As above
No action (alert)
As above
46
4711
Loss of Communication with Drive Board #11 As above
No action (alert)
As above
Configuration failure
47
70nn
Illegal configuration
Automatic, if configuration
is provided
Unit cannot be started
No factory configuration
48
80nn
Initial factory configuration required
Automatic, if configuration
is corrected
Unit cannot be started
Incorrect unit configuration
02: Defined unit size does not exist
03: Unit type or country incorrect configuration
(FACTORY)
04: Unit size is set to 0 (FACTORY)
05: Unit Tier incorrect configuration (FACTORY)
07: Hydronic kit option unavailable for this unit size
49
90nn
Master/Slave configuration error
Automatic, if master/slave
configuration returns to
normal or the unit returns to
the standalone mode
Master/Slave control
cannot be started
Configuration failure,
see section 9.6.2
Process failure
50
10001 Cooler Freeze Protection
Automatic (the first alarm
within 24 hours); otherwise,
Manual
Unit shuts down
No water flow, defective
thermistor
51
10005 Circuit A Low Suction Temperature
When the compressor is
“off”: Automatic (the first
alarm within 24 hours)
When the compressor is
“on”: Automatic (two alarms
within 24 hours); otherwise,
Manual
Circuit A shuts down
Pressure sensor defective,
EXV blocked or lack of
refrigerant
52
10006 Circuit B Low Suction Temperature
As above
Circuit B shuts down
As above
53, 54 10008,
10009
Circuit A High Superheat
Not applicable
-
-
55, 56 10011,
10012
Circuit B Low Superheat
Not applicable
-
-
57
10014 Customer Interlock failure
Automatic (the first alarm
within 24 hours); otherwise,
Manual
Unit shuts down
Customer interlock closed
when the unit is running
58
10028 Electrical Box Thermostat or Electrical
Interlock failure
Automatic, if the unit is not
running and the electrical
box input is closed
Unit shuts down
Electrical box input is open;
This alarm is triggered by
the electrical box input
linked to two serial inputs
in the electrical box
(electrical box thermostat
input and "customer"
interlock); by default, this
second input is closed
59
10030 Master/Slave communication Failure
Automatic, if communication
is re-established
Master/Slave control is
disabled and chillers return
to their stand-alone modes
CCN bus installation
defective
60
10031 Unit is in Emergency Stop
Automatic, if operating
conditions return to normal
Unit shuts down
Network emergency stop
command
61
10032 cooler Pump #1 default
Manual
Unit is restarted with another
pump running. If no pump is
available, the unit shuts down
Pump overheats or poor
pump connection
62
10033 cooler Pump #2 default
Manual
As above
As above
63
10037 Circ A - High Condensing temperature out of
map compressor
Manual
Circuit shuts down
Defective transducer
64
10038 Circ B - High Condensing temperature out of
map compressor
Manual
Circuit shuts down
Defective transducer
65
10050 Refrigerant Leakage Detection
Automatic, if the leakage
input voltage returns to
normal
No action (alert)
Refrigerant leak or leak
detector defective