9.6.4 - Compressor drive alarms/alerts
Compressor drive alarms or alerts are displayed based on
the following formula: 17+X-YYY for alarms and 35+X-YYY
for alerts (X stands for the number of the circuit and YYY
is the alarm/alert code).
The tables below present the most common alarms associated
with the variator malfunction. Please refer to the applicable
Danfoss documentation for more information on other
alarms.
Code
Description
Action to be taken
Drive alarms
4
Mains phase loss
Check the VFD supply voltage and the phase balance (±3%)
7
Over voltage
Contact Carrier Service
8
Under voltage
Contact Carrier Service
9
Inverter overloaded
Check the VFD output current/compressor current
12
Torque limit exceeded
Check the VFD output current/compressor current
13
Overcurrent
Check the VFD output current/compressor current
14
Earth fault
Check if an earth fault exists
16
Motor short-circuit
Check if there is a short-circuit at the VFD terminals
23*
Internal fan fault
Check the internal fan rotation
29
VFD temperature too high
Space temperature too high or VFD ventilation obstructed or damaged
30
Motor phase U missing
Check wiring of phase U
31
Motor phase V missing
Check wiring of phase V
32
Motor phase W missing
Check wiring of phase W
33
Inrush fault
Current demand too high: Let the VFD cool down for 20 minutes before starting it again
34
Fieldbus communication fault
Check the connections and the shielding of the serial communication cable
36
Mains failure
Check the VFD supply voltage and the phase balance (±3%)
38
Internal fault
Contact Carrier Service
47
24 V supply low
Contact Carrier Service
48
1.8 V supply low
Contact Carrier Service
65
Control board over temperature
Check the space temperature and the VFD fan
67
Option configuration has changed
Contact Carrier Service
68
Emergency stop
Contact Carrier Service
80
Drive initialized to default value
Contact Carrier Service
95
Torque loss
Contact Carrier Service
243
IGBT defective
Contact Carrier Service
251**
New parts detached
Contact Carrier Service
Drive alerts
3
No motor
Check the motor connections
4
Mains phase loss
Check the VFD supply voltage and the phase balance (±3%)
5
DC link voltage high
Check the VFD supply voltage and the phase balance (±3%)
6
DC link voltage low
Check the VFD supply voltage and the phase balance (±3%)
7
DC over voltage
Contact Carrier Service
8
DC under voltage
Contact Carrier Service
9
Inverter overloaded
Check the VFD output current/compressor current
12
Torque limit exceeded
Check the VFD output current/compressor current
13
Overcurrent
Check the VFD output current/compressor current
14
Earth fault
Check if an earth fault exists
23*
Internal fan fault:
Compressor drive: The drive will be stopped
immediately.
Fan drive: The drive continues to operate.
Check the internal fan rotation
34
Fieldbus communication fault
Check the connections and the shielding of the serial communication cable
36
Mains failure
Check the VFD supply voltage and the phase balance (±3%)
47
24 V supply low
Contact Carrier Service
49
Motor speed limit exceeded
Contact Carrier Service
59
Current limit exceeded
Check the VFD output current/compressor current
62
Output frequency at maximum limit
Check the VFD output current/compressor current
64
Voltage limit
Supply voltage too low
65
Control board overtemperature
Check the space temperature and the VFD fan
66
Heat sink temperature low
Space temperature too low
90†
Encoder loss
Contact Carrier Service
95
Torque loss
Contact Carrier Service
96
Start delayed
Contact Carrier Service
97
Stop delayed
Contact Carrier Service
98
Clock fault
Contact Carrier Service
243
IGBT defective
Contact Carrier Service
247
Capacity board temperature
Contact Carrier Service
*
Error 24 and 104 possible
** Error 70 or 250 possible
†
Not applicable to variator size 102