37
JBus
code
Alarm
code Description
Reset type
Action taken
Possible cause
66
10067 Circuit A Low Oil Pressure
Automatic (3 alarms within
24 hours); otherwise,
Manual
Compressor shuts down
Pressure sensor fault,
defective wiring or oil filter
installation fault
67
10068 Circuit B Low Oil Pressure
As above
Compressor shuts down
As above
68
10070
Circuit A Max Oil Filter Differential Pressure
Manual
Compressor shuts down
As above
69
10071
Circuit B Max Oil Filter Differential Pressure
Manual
Compressor shuts down
As above
70
10073 Condenser Pump #1 default
Not applicable
-
-
71
10074 Condenser Pump #2 default
Not applicable
-
-
72
10075 Circuit A Low Oil Level
When compressor is “off”:
Automatic
When compressor is “on”:
Automatic (3 alarms within
24 hours)
Circuit A shuts down
Oil level too low or oil level
detector defective
73
10076 Circuit B Low Oil Level
As above
Circuit B shuts down
As above
74
10078 Circuit A High Discharge Gas Temperature
Manual
Circuit A shuts down
Defective transducer, max.
condensing temperature
setpoint too low or
refrigerant charge too high
75
10079 Circuit B High Discharge Gas Temperature
Manual
Circuit B shuts down
As above
76
10081 Circuit A Suction Valve closed
Manual
Circuit A shuts down
Economizer pressure
transducer defective,
suction valve fault
77
10082 Circuit B Suction Valve closed
Manual
Circuit B shuts down
As above
78
10084 Circuit A High Oil Filter Drop Pressure
Manual
No action (alert)
Oil filter should be checked
79
10085 Circuit B High Oil Filter Drop Pressure
Manual
No action (alert)
As above
80
10090
Cooler Flow Switch Setpoint Configuration
Failure
Manual
Unit is not allowed to start
Defective flow controller or
wiring error
81
10091 Cooler Flow Switch Failure
Automatic (the first alarm
within 24 hours); otherwise,
Manual
Compressors and the
evaporator pump are
stopped
As above
82
10097
Water Exchanger Temperature Sensors
Swap
Manual
Unit shuts down
Leaving water temperature
is higher than entering
water temperature
83
10106 Circ A - High saturated temperature out of
map compressor
Manual
Circuit A shuts down
Coil fouling
84
10107 Circ B - High saturated temperature out of
map compressor
Manual
Circuit B shuts down
Coil fouling
85
10110 Lack of Refrigerant suspected on circuit A
Automatic, if fault conditions
are no longer present
(3 alarms within 24 hours);
otherwise, Manual
No action (alert)
Refrigerant leak suspected.
Contact Carrier Service
86
10111 Lack of Refrigerant suspected on circuit B
As above
No action (alert)
As above
87
10113 Compressor frequency below min frequency
threshold - Circuit A
Automatic (the first alarm
within 24 hours); otherwise,
Manual
Circuit A shuts down
Check drive alarms and
compressor current
consumption
88
10114 Compressor frequency below min frequency
threshold - Circuit B
As above
Circuit B shuts down
As above
89
10116 Discharge superheat too low - Circuit A
Manual
Circuit A shuts down
EXV wiring swapped
90
10117 Discharge superheat too low - Circuit B
Manual
Circuit B shuts down
As above
91
11208
Cooler Water Loop : Pressure sensor
Crossed
Automatic, if flow switch is
closed; Manual, if flow
switch is open
Unit shuts down
Flow switch open
92
14000
Over flow in cooler hydraulic kit
Automatic, if water flow
gets below the maximum
flow configured
No action (alert)
Water loop pressure drop
too low
Service maintenance
93
13nnn Service maintenance alert Number # nnn
Manual
No action (alert)
Preventive maintenance
date has passed; servicing
action required; contact
Carrier Service Agency
VFD failure
94
17nnn Circuit A Compressor VFD Failure
Manual
Circuit A shuts down
95
18nnn Circuit B Compressor VFD Failure
Manual
Circuit B shuts down
96
20nnn Circuit A Fan VFD 1 Failure
Manual, except for alarm
20027 (Automatic reset)
Circuit A shuts down
97
21nnn Circuit A Fan VFD 2 Failure
As above
Circuit A shuts down
98
22nnn Circuit A Fan VFD 3 Failure
Not applicable
-
-
99
23nnn Circuit B Fan VFD 1 Failure
Manual, except for alarm
23027 (Automatic reset)
Circuit B shuts down
100
24nnn Circuit B Fan VFD 2 Failure
As above
Circuit B shuts down
101
25nnn Circuit B Fan VFD 3 Failure
Not applicable
-
-
102
26nnn Hydronic kit pump 1 VFD Failure
Manual, except for alarm
26027 (Automatic reset)
Unit shuts down
103
27nnn Hydronic kit pump 2 VFD Failure
As above
Unit shuts down