Installation
10
RTU-MP Controller
Wire specifications
○
A dedicated 22 or 24 AWG shielded twisted pair wire (EIA 485)
○
Maximum wire length 2000 feet (610 meters) or 32 nodes
○
Devices should be daisy-chained and not star-wired
○
Attach the drain/shield wire to both ends of the network segment and through every controller
NOTE
Use the same polarity throughout the network segment.
7
Turn
on
the RTU-MP's power.
LonWorks
When you handle the LonWorks Option Card:
•
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
•
Do not touch components or leads.
•
Handle the board by its edges.
•
Isolate from high voltage or electrostatic discharge.
•
Ensure that you are properly grounded.
Refer to
Appendix E
(page 49) for the LonWorks Protocol Implementation Conformance Statement (PICS).
Configuring the RTU-MP for LonWorks Option Card
1
Turn
off
the RTU-MP's power.
NOTES
○
Changes made to the switches when the RTU-MP is on will not take effect until the RTU-MP has
been power cycled!
○
The controller’s rotary address switches are not used when the LON-OC is installed. That’s because
each LON-OC has a 48-bit Neuron ID that makes it unique on the LonWorks network.