Appendix B - BACnet Protocol Implementation Conformance Statement
44
RTU-MP Controller
4. Writeable Properties:
Schedule (ENUM) and Schedule (UNS):
description
effective_period
exception_schedule
present_value
priority_for_writing
relinquish_default
weekly_schedule
5. Proprietary properties:
None
6. Range Restrictions:
description
limited to 50 octets in length
exception_schedule
limited to 30 BACnetSpecialEvents
each being limited to 6 BACnetTimeValues
present_value
0 to 4294967295
relinquish_default
0 to 4294967295
weekly_schedule
limited to 6 BACnetTimeValues per BACnetDailySchedule
Trend_log
1. Creatable?
Trend_log:
NO
2. Deletable?
NO
3. Optional Properties
Supported:
acked_transitions
client_cov_increment
cov_resubscription_interval
current_notify_time
description
event_enable
event_time_stamps
log_device_object_property
log_interval
notification_class
notification_threshold
notify_type
previous_notify_time
records_since_notification
start_time
stop_time
4. Writeable Properties:
buffer_size
client_cov_increment
cov_resubscription_interval
description
event_enable
log_enable
log_interval
notification_class
notification_threshold
notify_type
record_count
start_time
stop_time
stop_when_full
total_record_count
5. Proprietary properties:
None
6. Range Restrictions:
description
limited to 50 octets in length
log_interval
0 to 4294967295
notification_class
must be valid notification_class
notification_threshold
0 to 4294967295
record_count
can only be written to 0
total_record_count
can only be written to 0
Содержание RTU-MP
Страница 2: ......
Страница 6: ...Introduction 2 RTU MP Controller...
Страница 54: ......
Страница 56: ......
Страница 57: ......