RTU-MP Controller
11
2
Set the Comm Selector DIP Switches
DS1
and
DS2
on
SW3
for 38.4k Communications speed. This is
the speed at which the LON-OC speaks to the RTU-MP. It is fixed at 38.4k.
3
Set the Comm Selector DIP Switches
DS3
through
DS6
on
SW3
for LonWorks. See example below.
4
Set the Comm Selector DIP Switch
DS7
on
SW3
to the ON position to enable the LON-OC.
5
Leave Comm Selector DIP Switch
DS8
on
SW3
in the OFF position since it is not used.
SW3 Protocol Switch Settings for LonWorks
DS8
DS7
DS6
DS5
DS4
DS3
Off
On
On
Off
On
Off
The following example shows the DIP Switches set for 38.4k baud and the LON-OC enabled.
6
Plug the LON-OC's ribbon cable into Comm Option Port
J15
on the RTU-MP. See illustration below.
CAUTION!
The controller must be
OFF
before being connected.
7
Turn
on
the RTU-MP's power.
8
Commision the RTU-MP for LonWorks communication. See instructions below.