Appendix B - BACnet Protocol Implementation Conformance Statement
38
RTU-MP Controller
Binary Output:
5. Proprietary properties:
None
6. Range Restrictions:
active_text
limited to 50 octets in length
change_of_state_count
0 to 4294967295
description
limited to 50 octets in length
device_type
limited to 50 octets in length
elapsed_active_time
0 to 4294967295
inactive_text
limited to 50 octets in length
minimum_off_time
0 to 4294967295
minimum_on_time
0 to 4294967295
notification_class
must be valid notification_class
time_delay
0 to 4294967295
Binary Value (PAR), (CLOCK), and (STAT)
Binary Value (PAR) and Binary Value (CLOCK):
1. Creatable?
NO
2. Deletable?
NO
3. Optional Properties
Supported:
acked_transitions
active_text
alarm_value
change_of_state_count
change_of_state_time
description
elapsed_active_time
event_enable
event_time_stamps
inactive_text
minimum_off_time
minimum_on_time
notification_class
notify_type
priority_array
reliability
relinquish_default
time_delay
time_of_active_time_reset
time_of_state_count_reset
4. Writeable Properties:
active_text
alarm_value
change_of_state_count
description
elapsed_active_time
event_enable
inactive_text
minimum_off_time
minimum_on_time
notification_class
notify_type
out_of_service
present_value
relinquish_default
time_delay
5. Proprietary properties:
None
6. Range Restrictions:
active_text
limited to 50 octets in length
change_of_state_count
0 to 4294967295
description
limited to 50 octets in length
device_type
limited to 50 octets in length
Содержание RTU-MP
Страница 2: ......
Страница 6: ...Introduction 2 RTU MP Controller...
Страница 54: ......
Страница 56: ......